I bought a big 2P cabinet air conditioner, but what should I do if the wall socket type 10A

Updated on home 2024-04-02
16 answers
  1. Anonymous users2024-02-07

    Theoretically, 1p is equal to power, which is the power of the compressor, but in addition to the compressor, the air conditioner also has internal and external fan motors, circuit boards and other accessories, so together, the power should be more than 800 about 1500w, and about 2p1800w.

    So if the voltage level of the air conditioner is 220V, it is the current per kilowatt. At 380V, it is 2A.

    Theoretical calculations, 2

    However, this is only a theoretical calculation, and the normal operation depends on the ambient temperature, set temperature, and so on. That is to say, the actual current may be higher than calculated, so a 10A socket is not very safe. To give you a suggestion, if the cable of the wall socket is greater than or equal to the square, then replace the socket with 16 or 20A, if the cable is smaller, the cable is a little thin, and it can only be connected to other methods such as temporary power supply.

  2. Anonymous users2024-02-06

    No, it is best to install 32A air open, socket 10A is not safe, if the current is 18A when heating, if you have to install, you must install a 16A socket. Remember to add 10 points to me.

  3. Anonymous users2024-02-05

    This depends on what specifications the wire of the existing socket is, if it is more than square millimeters, then it is not a big problem for you to do this, if it is square, it is not safe, the wire will be hot current, it is recommended to find an electrician to pull a wire more than square from the empty box.

  4. Anonymous users2024-02-04

    Take out the 10A one, and replace it with a 16A one, and then turn off the power supply.

  5. Anonymous users2024-02-03

    The current of the air conditioner is 3-8 times that of normal operation, and the 10A socket is easy to burn out, find an electrician to replace it for you.

  6. Anonymous users2024-02-02

    No, there is no plug when it leaves the factory, and its purpose is that it is not safe to use the plug, just change it to an empty one.

  7. Anonymous users2024-02-01

    It is okay for an air conditioner (about 5200 watts) to use a 10 amp outlet, but you need to make sure of the following:

    It is sure that the quality of the sockets and wires of the high dismantling guarantee meets the safety standards and can withstand the current load of the air conditioner.

    The rated current of the air conditioner does not exceed the rated current of the socket (10 amps). Generally, the rated current of the air conditioner is between 6-8 amps, and a 10 amp socket can be used.

    In order to ensure the safe use of the air conditioner, it is recommended to install a suitable air switch (such as 16 amps or 20 amps) on the power cord to prevent the air conditioner from overloading, short circuit and other abnormal conditions.

    If you are unsure whether the socket is suitable for use with air conditioning, it is recommended to consult a professional electrician for inspection and evaluation. When installing air conditioners, follow electrical safety codes and operating procedures to ensure safety.

  8. Anonymous users2024-01-31

    There is no problem with the air conditioner with a 10A outlet. For the sake of safety, most of the household sockets still use 16A sockets.

    A 10A socket means that it can be rated to use a current of 10A, a voltage of 220V for household use, and a 2500 watt electrical appliance is about 10A current, and a 10A socket is strictly forbidden to use electrical appliances above 2500 watts.

    The horsepower of the air conditioner refers to the power consumption of electrical appliances, 1 horsepower = 1 horsepower = 735w, and horsepower does not refer to the cooling capacity. Usually how many horsepower of the air conditioner is estimated, the cooling capacity of the air conditioner is estimated according to the power consumption of the air conditioner. Generally speaking, it is customary to use 1 horsepower equal to 2500W of cooling capacity, and horsepower is about equal to 3500W of cooling capacity; 2600W is about horsepower, 2700W model is horsepower, 2800W model is about horsepower, 3200W model is horsepower; The 3300W model is about horses, and the 3600W model is a large horse.

  9. Anonymous users2024-01-30

    Single-phase 220V air conditioner Power Rated current 9A Considering the starting shock 15A

    10A sockets can be used but are on the small side, it is recommended to use 15A sockets or above.

  10. Anonymous users2024-01-29

    No, the maximum power of the 2P air conditioner is about 4150W, and the current is.

    Take Gree 2HP Inverter Q Platinum Vertical Cabinet Air Conditioner KFR-50LW (50596) FNAA-A3 as an example, its power is 1650W, cooling power is 2350W+ electric heating power 1800W.

    When calculating the load, it should be calculated according to the maximum power: 2350 + 1800 4150W to calculate the current: ijs = p u cos = 4150 220 ;

    25A switches and sockets should be used.

  11. Anonymous users2024-01-28

    The 2P air conditioner should not be a 10A plug, is it the installer who installed the wrong one, (some manufacturers of 2P air conditioners are not equipped with plugs when they leave the factory), but if it is wrong, it is recommended to change to a 16A plug, 2P air conditioner has high power, and it is not safe to heat up after a long time with a 10A plug, and the plug must also use a special air conditioner, which is a 16A plug, which is sold in large supermarkets.

  12. Anonymous users2024-01-27

    No!

    And the 10-amplification row may not be able to plug in the air conditioner!

    Because a 10 amp socket has a total current of 10 amps, not every jack is 10 amps!

    Moreover, the air conditioner is an inductive electrical appliance, and the starting current is more than twice the normal working force!

    10. Although the placement row can be used on the surface, there are unsafe factors:

    High-power appliances are not allowed to share sockets!

    Therefore, please use a special air conditioning socket above 15 amps!

    Lonely mountain man.

  13. Anonymous users2024-01-26

    No, you must use a 16A socket, it is best to take a special line, do not use a socket, otherwise it is easy to cause the plug to burn.

  14. Anonymous users2024-01-25

    The input power of the 2P air conditioner is about 735*2=1470 kilowatts, and the working current is less than 10 amps, which can be used, but it is better to use 16A.

  15. Anonymous users2024-01-24

    If you look at the data on the plug of the air conditioner, if it is 10A, it can be used. If not, you have to match the socket strip according to the plug data.

  16. Anonymous users2024-01-23

    10A no, it depends on the maximum current of the air conditioner to decide

Related questions
7 answers2024-04-02

How many horses does the air conditioner have? What does 1 horse or 2 horses mean? I finally figured it out today.

9 answers2024-04-02

About 4000-5000 yuan, the best Gree in China at present!

7 answers2024-04-02

Why does it take a long time for P2P platforms to collect payments?

8 answers2024-04-02

The concept of P2P.

P2P is an abbreviation for peer-to-peer, which means "equal", "colleague" and "partner" in English. In this way, P2P can also be understood as "partner-to-partner", or peer-to-peer. At present, it is considered to have great prospects in strengthening the communication of people on the network, the exchange of documents, and the calculation of distribution. >>>More

2 answers2024-04-02

That's how the ARP virus came about