How much can the maximum current of the transformer be used in 630KVA?

Updated on science 2024-03-16
11 answers
  1. Anonymous users2024-02-06

    How much can the maximum current of transformer 630kva be used Solution:

    The maximum current of a 630kVA transformer depends on the rated voltage on the low voltage side.

    The value is determined.

    If the rated voltage on the low voltage side of the 630kVA transformer is 400V, according to the capacity S voltage * current, it can be calculated:

    Current rating. i 6300 (kiloamperes 9100 amps, the maximum long-term current that each phase can withstand is 9100A.

    Overload operation is allowed in a short period of time, and the allowable amount is inversely proportional to time and load rate, and the maximum overload is 20% within 2 hours.

    That is, the maximum allowable current of 9100*(1+20%) 10900A within 2 hours.

    How much power can be used in a 630kva transformer:

    Without additional measures, the 630kVA transformer can use up to 420kW power appliances.

    Transformer power factor.

    Generally, there are also there), then, the total power of the transformer = 630*.

    According to the Power Engineering Design Manual

    Transformer capacity, for a single transformer with stable load power supply, the load rate is generally about 85%, therefore, in the above example, the electrical power = 504 * 85% =.

    If it is a single large.

    Power motors, due to the large starting current, even if measures are taken, the power consumption should be reduced accordingly.

    If the three phases are unbalanced.

    It is also necessary to reduce the power consumption accordingly.

  2. Anonymous users2024-02-05

    630kva=504kw, according to the formula for calculating the three-phase active power (low-voltage side current i=active power 504kw 3 voltage 400v power factor, according to the transformer energy conservation law, voltage ratio (10kv times), so high-voltage side current = low-voltage side current.

  3. Anonymous users2024-02-04

    This question is up to me, it takes a little time to type, so please be patient.

  4. Anonymous users2024-02-03

    Summary. 1. Rated current of 630kva transformer.

    1. The voltage and current values on all transformer name plates are wireless. Because the user of the transformer is concerned about the use, the transformer manufacturer gives the value of line voltage and line current. But in transformer design and manufacturing, he calculates the voltage and current of each phase.

    So, he is concerned with the phase voltage and the phase current.

    2. The relationship between the line and the phase depends on the connection of the coil. Now the general distribution transformer is DYN11 connection. The high voltage is a D connection (triangle connection).

    Feature: The line voltage is equal to the phase voltage. The line current is equal to the phase current which is 3 times the root number. The low voltage is Y-connection (star connection), which is characterized by the line voltage being equal to 3 times the root number of the phase voltage, and the line current being equal to the phase current.

    3. For example: 630kva transformer, the low voltage is 400V (line) The output line current is: I2 line = 630 The low voltage is Y, and the phase current is equal to the line current.

    Therefore, this method is also used for phase current, and the current of high-voltage lines and phases can also be calculated.

    1) Secondary side rated current: i 630000 400.

    2) Primary side rated current: i 630000 10000.

    3) Maximum output power p=630*press.

    4) Maximum output power p=630*press.

    How much current can be used for a transformer 630 kVA?

    1. The rated current of 630kva transformer 1. The voltage and current values on all transformer name plates are wired. Because the user of the transformer is concerned about the use, the transformer manufacturer gives the value of line voltage and line current. But in transformer design and manufacturing, he calculates the voltage and current of each phase.

    So, he is concerned with the phase voltage and the phase current. 2. The relationship between the line and the phase depends on the connection of the coil. Now the general distribution transformer is DYN11 connection.

    The high voltage is a D connection (triangle connection). Feature: The line voltage is equal to the phase voltage.

    The line current is equal to the phase current which is 3 times the root number. The low voltage is Y-connection (star connection), which is characterized by the line voltage being equal to 3 times the root number of the phase voltage, and the line current being equal to the phase current. 3. For example:

    For a transformer of 630kva, the low voltage is 400V (line) The output line current is: I2 line = 630 The low voltage is Y, and the phase current is equal to the line current. Therefore, this method is also used for phase current, and the current of high-voltage lines and phases can also be calculated.

    1) Secondary side rated current: i 630000 400. (2) Primary side rated current:

    i=630000÷10000÷。3) Maximum output power p=630*press. 4) Maximum output power p=630*press.

    The rated current of the transformer with a grate of 630kva is 10,000 volts or 35,000 volts on the primary side. The secondary side is 400 volts. 1.

    When the primary side voltage is 10,000 volts, then i = 630,000 (amps) according to ps=. 2.When the primary voltage side is 35,000 volts, i=630,000 (amps.)

    3.Whether the primary side voltage is 10,000 volts or 35,000 volts, the secondary side current, i=630,000 (amps.

  5. Anonymous users2024-02-02

    Dear, hello, I am glad to answer for you how much can the maximum current of transformer 630kva be used? Answer: The maximum current of transformer 630kva is 890a, the calculation is that 1kva is a current, the calculation of 630kva is 890a, the maximum current of transformer 630kva is 890a, the calculation is 1kva is a current, 630kva is calculated to get 890a, the maximum current of transformer 630kva is 890a, the calculation is 1kva is a current, and the calculation of 630kva is 890a, thank you.

  6. Anonymous users2024-02-01

    Summary. Hello dear, happy to answer for you.

    The nominal capacity of the nameplate of the three-phase power transformer is the apparent power, and under normal circumstances, it is converted into the conversion efficiency that should be considered when converted into active power, so that it can not actually carry 630kw of active power.

    With 630.

    How many kW can a 630kva transformer carry

    Hello dear, I am glad to answer for you that 630kva transformer can bring 535kw three-phase power transformer nameplate with nominal capacity as apparent power, under normal circumstances, it is converted into active power should consider the conversion efficiency, so that it can not actually carry 630kw active power. With 630.

    I hope mine can help you, I wish you a happy life and a happy life, oh and <><

  7. Anonymous users2024-01-31

    Summary. Kiss! If the rated voltage is 10.

    Primary side rated current:

    i p Secondary side current rating:

    The power factor of the transformer of i p 630kva is generally (and there are), then, the total power of the transformer = 630*.

    According to the "Power Engineering Design Manual", transformer capacity, for a single 630kva transformer with stable load power supply, the load rate is generally about 85%, therefore, in the above example, the electrical power = 504 * 85% =.

    If it is a single high-power motor, due to the large starting current, even if measures are taken, the electrical power should be reduced accordingly.

    If the three phases are unbalanced, the power consumption should also be reduced accordingly.

    Short overloads are allowed.

    How much current can a 630 transformer load.

    Kiss! If the rated voltage is 10. Primary side rated current:

    i p secondary side rated current: i p transformer power factor is generally (and there are), then, the total power of the transformer = 630*. According to the "Power Engineering Design Manual", transformer capacity, for a single 630kva transformer with stable load power supply, the load rate is generally about 85%, therefore, in the above example, the electrical power = 504 * 85% =.

    If it is a single high-power motor, due to the large starting current, even if measures are taken, the electrical power should be reduced accordingly. If the three phases are unbalanced, the power consumption should also be reduced accordingly. Short overloads are allowed.

    Kiss! For the sake of safety, please use it according to the rated voltage and wish you a happy life<>

    Hello, because seeing that you did not rate me last time, I am very concerned about your experience. If you are satisfied with my service, I hope you can give a thumbs up! If there is a problem, I am always waiting for you. I wish you a happy life and a happy life!

  8. Anonymous users2024-01-30

    Hello dear and happy to answer for you. How many kilowatts can a 630kva transformer carry? If the transformer is all electrically heated (resistive) loads, theoretically it can carry a load of 630 kilowatts.

    However, according to the regulations of the Electricity Bureau, the maximum load is 85% of the full load, which is 535kva. If all are inductive loads such as motors, it is generally 6 discounts, that is, 378 kilowatts of motor loads, if both loads are available, then 7 discounts (441kw) or 8 folds (504kw), it depends on which load accounts for more proportions. In fact, according to the regulations of the Electricity Bureau, the maximum load cannot exceed 535kva.

    Hope mine is helpful to you! Don't forget to give it a thumbs up! I wish you a happy life, peace and joy!

  9. Anonymous users2024-01-29

    Summary. According to the power factor, according to the "Electric Power Engineering Design Manual", the transformer capacity, for a single transformer with stable load power supply, the load rate is generally about 85%, and the power of electrical appliances = 504 * 85% =. This is equivalent to approximately 420kw.

    The capacity of the transformer is an apparent power (with kVA). The unit of electrical appliances is active power ((kw), and there is a difference between the two. Because there is still reactive power when the power supply system is running.

    Generally speaking, the capacity * power factor of a transformer is the capacity of the electrical equipment it can carry.

    How much current can be used for a transformer 630 kVA?

    Hello dear, it is my honor to answer your questions, it will take a little time to sort out the answers, please be patient

    The 630kva transformer can carry about the first current, the transformer is simply a device that uses the principle of electromagnetic induction to change the AC voltage, and the main components are the primary coil, the secondary coil and the iron core (magnetic core).

    The general power factor is calculated as p=s*cos =630*transformer energy band kilowatts.

    According to the power factor, according to the "Electric Power Engineering Design Manual", the transformer capacity, for a single transformer with stable load power supply, the load rate is generally about 85%, and the power of electrical appliances = 504 * 85% =. This is equivalent to approximately 420kw. The capacity of the transformer is an apparent power (with kVA).

    The unit of electrical appliances is active power ((kw), and there is a difference between the two. Because there is still reactive power when the power supply system is running. Generally speaking, the capacity * power factor of a transformer is the capacity of the electrical equipment it can carry.

  10. Anonymous users2024-01-28

    Summary. Hello dear!

    The rated current is I=6300 (kA = 9100A, and the maximum long-term current that each phase can withstand is 9100A.

    Overload operation is allowed in a short period of time, and the allowable amount is inversely proportional to time and load rate, and the maximum overload is 20% within 2 hours.

    That is, the maximum allowable current of 9100*(1+20%) 10900A within 2 hours.

    What is the maximum power appliance that can be used in a 630kVA transformer: Without additional measures, a 630kVA transformer can use a maximum of 420kW power appliance.

    How much current can a 630kVA transformer withstand?

    Current Rating & Capacity**

    Rated current: i=6300 (kA=9100A.)

    Maximum long-term current per phase: 9100 amps.

    Overload capacity**

    Overload operation is allowed for short periods of time.

    The permissible overload is inversely proportional to the time and load rate.

    A maximum of 20% overload is allowed within 2 hours

    Maximum withstand current in 2 hours: 9100 (1+20%)=10900 amps.

    Maximum power carrying capacity of 630kVA transformer**

    Without additional measures: up to 420 kW power appliances can be used.

    Hello, dear users!

    If you are satisfied with me, please click the "" button in the upper right corner, which will be the greatest encouragement to me. If you still have any questions or need further information, please feel free to ask me.

    Finally, I wish you all the best and a happy life!

  11. Anonymous users2024-01-27

    Summary. How many kW can a 630kva transformer carry

    0kva transformer with 400kw load, no problem at all.

    KVA is the apparent power (or nominal power) of the transformer. is the sum of the active power and the reactive power (is the geometric sum, that is, the vector sum, not the algebraic sum).

    kW is the total active power consumption of your load.

    3. If the power factor of your load is 80% (generally the minimum requirement, after compensation, it will be greater than 80%). Then, the apparent power of the transformer he needs is: p=400 <630kva.

    If you choose a 500kVA transformer, it can also meet the requirements. And the choice of 630kva is to leave room for improvement. Hope it helps!

    How many kW can a 630kva transformer carry

    How many kw can 630kva transformer carry, hello! The power factor of 630kva transformer is generally (and there are), then, the total power of the transformer = 630*. Hope it helps!

    How many kws can a 630kva transformer carry 0kva transformer with a load of 400kw is no problem kva is the apparent power (or - nominal power) of the transformer. is the sum of the active power and the reactive power (is the geometric sum, that is, the vector sum, not the algebraic sum).

    kW is the total active power consumption of your load. 3. If the power factor of your load is 80% (generally the minimum requirement, after compensation, it will be greater than 80%). Then, the apparent power of the transformer he needs is:

    p=400/<630kva。If you choose a 500kVA transformer, it can also meet the requirements. And the choice of 630kva is to leave room for improvement.

    Hope it helps!

    If my answer is helpful to you, please give it a thumbs up (comment in the bottom left corner), your efforts are important to me, and your support is also my motivation for progress. Wishing you good health and a happy mood!

Related questions
6 answers2024-03-16

Upstairs is too mother-in-law, 10kv if the primary current is YJV22-10 3*25. >>>More

10 answers2024-03-16

Hehe. If you already have an off-the-shelf power distribution device that also has a compensation device, then you should set the power factor removal point of the compensation device at it. That is to say, when compensating, when the power factor is exceeded, the capacitor will not be invested, and the capacitor will be cut off if it is higher. >>>More

12 answers2024-03-16

It may be that a vortex has been generated.

For example, if an insulated wire is wound around an iron core, and after the alternating current is turned on, the current becomes a closed loop in the metal block. >>>More

26 answers2024-03-16

Full-power step-up transformers and step-down transformers can be used interchangeably. If the transformer reaches full power, it will not cause damage, if the copper-clad aluminum wire or aluminum wire transformer cannot be used in this way, because the power of these two types of transformers is not as sufficient as the power of the all-copper wire transformer. >>>More

7 answers2024-03-16

The isolation transformer is a safety power supply, which is generally used for machine repair and maintenance, and plays the role of protection, lightning protection and filtering. >>>More