Can the hazardous chemicals warehouse be built with high side windows?

Updated on society 2024-03-28
6 answers
  1. Anonymous users2024-02-07

    According to the regulations: 1. The store of the retail industry should be kept at a distance of more than 500m from the bustling commercial area or the densely populated area.

    The operating area of the retail business (excluding the warehouse) shall not be less than 60 square meters, and there shall be no living facilities in the store. 2. Large and medium-sized hazardous chemical warehouses should be kept at least 1000m away from surrounding public buildings, traffic arteries (highways, railways, waterways), industrial and mining enterprises, etc.; Large and medium-sized hazardous chemicals warehouses should be set up in the reservoir area and living area, and there should be a physical fence of more than 2m between the two areas, and the distance between the wall and the building in the reservoir area should not be less than 5m, and the fire distance between the fenced buildings should be met;

    3. The inventory of hazardous chemicals should be kept at the corresponding stack distance, wall distance and column distance. The spacing between the stacks is not less, and the spacing between the buttresses and the walls and columns is not small. The width of the main aisle is not small;

  2. Anonymous users2024-02-06

    1. Large and medium-sized hazardous chemical warehouses should be located far away from urban areas and residential areas, when in the downwind direction of the dominant wind direction and the downstream of the river.

    2. Large and medium-sized hazardous chemical warehouses should be kept at least 1000m away from surrounding public buildings, traffic arteries (highways, railways, waterways), industrial and mining enterprises, etc.;

    3. Large and medium-sized hazardous chemicals warehouses should be set up in the reservoir area and living area, and there should be a physical fence of more than 2m between the two areas, and the distance between the wall and the building in the reservoir area should not be less than 5m, and the fire distance between the fenced buildings should be met.

    Hazardous chemical warehouses are divided into three types according to their use nature and business scale: large warehouses (with a total area of more than 9,000 m2 of warehouse or freight yard); Medium-sized warehouses (with a total area of 550 m2 and 9,000 m2 of warehouse or yard); Small warehouses (with a total area of less than 550 m2 in the warehouse or yard).

  3. Anonymous users2024-02-05

    Look at the fire protection category of your dangerous goods. According to GB50016-2006, the minimum of general Class A warehouses and civil buildings shall not be less than 25M, and not less than 10M outside Class A.

  4. Anonymous users2024-02-04

    In 2001, the State Administration of Work Safety promulgated the "Conditions and Technical Requirements for the Opening of Hazardous Chemicals Business Enterprises GB 18265" as follows:

    Large and medium-sized hazardous chemical warehouses should be kept at least 1,000 meters away from surrounding public buildings, transportation arteries (highways, railways, waterways), industrial and mining enterprises, etc.

  5. Anonymous users2024-02-03

    1. In terms of structure, material and area, it is necessary to refer to the "Code for Fire Protection Design of Buildings" (GB50016-2006), and the fire resistance level should be above level 2, generally brick walls, concrete roofs, and outward-opening iron doors. The total area of the warehouse cannot be greater than 750, the area of each compartment cannot exceed 250, and the warehouse must be single-storey.

    2. The fire spacing also refers to the "Code for Fire Protection Design of Buildings", and the distance between the office and dormitory and other civil buildings is greater than 25m (when the reserve is less than 10t), the distance between the brick and concrete structure is more than 12m, and the distance between the steel frame (not brushed with fireproof coating) is more than 15m.

    3. Electrical facilities. It is best not to install any electrical facilities in the warehouse. It is enough to open a few shutters at the bottom of the walls on both sides to meet the ventilation requirements.

    If you want to install electric lights, exhaust fans, etc., you must choose explosion-proof products, the power cord should be sealed with galvanized steel water pipes, the connection parts should be transitioned with flexible explosion-proof pipes, and the sealed pipes should be grounded. Switches and sockets should be installed outside the warehouse. The installation location of the exhaust fan should also be at the bottom of the warehouse wall, because the vapor density emitted by paint, water and so on is greater than that of air, and combustible vapor will accumulate on the ground accessories.

    4. Exhaust fan. Many companies are concerned that when exhaust fans and blinds are installed near the ground, people will litter cigarette butts. In this case, it is recommended to install the explosion-proof exhaust fan on the top of the warehouse, and then install a ventilation pipe in the warehouse to lead to the bottom of the warehouse to facilitate the extraction of the vapor accumulated on the ground.

    5. A slope of about 10cm should be set at the door of the warehouse to prevent the flammable liquid from flowing to the outside and causing a fire when the packaging is damaged. Considering that a rickshaw may be used for transportation, it is recommended to build the slope into a slope shape to facilitate access.

    6. Under the premise that the land area is sufficient, the warehouse should be as spacious as possible to meet the requirements of commodity placement, and the goods should be stacked above the wall, above the stacking spacing of various items, above the main passage and above the branch passage.

    It can be seen that the hazardous chemicals warehouse cannot be set up on the roof. Even if you set it, it is impossible to pass the safety assessment.

  6. Anonymous users2024-02-02

    No, many chemicals are prone to accidents when exposed to light and high temperatures.

Related questions
5 answers2024-03-28

Enterprises engaged in the production, storage, use, operation and transportation of chemicals, involving chemicals that are flammable, explosive, toxic and harmful and corrosive, and cause harm or damage to personnel, facilities and the environment. The enterprise is a hazardous chemical enterprise. >>>More

8 answers2024-03-28

1. Handle hazardous chemical certificates for refined oil products. >>>More

4 answers2024-03-28

Fishmeal is not classified as a dangerous good, and hazardous material is flammable, explosive, highly corrosive, toxic and radioactive. >>>More

10 answers2024-03-28

Any dangerous goods export by sea is inseparable from these 4 basic processes: >>>More

9 answers2024-03-28

The finished products to be put into storage are typed by the terminal operator of the warehousing terminal into the product name, specification model and quantity. The control system receives the storage data through the man-machine interface, and automatically allocates a cargo location and prompts the storage roadway according to the principles of uniform distribution, first down and then up, lower heavy and lighter, nearby warehousing, ABC classification and principles. According to the prompts, the porter can send the goods loaded on the standard pallet from the small battery truck to the storage platform of the roadway. >>>More