-
1. Connect the transmitter in series to the leakage wire, and ensure that one clip of the transmitter is connected to the positive power supply of the circuit.
2. Press the switch of the transmitter to the tone position.
3. Turn on the detector sound adjustment switch and adjust the volume of the sound to the appropriate volume.
4. Use the detector to slowly sweep the wire, conduit, etc., ensure that the detector's probe head is perpendicular above or below the measured wire, and make the probe head as close to the tested wire as possible, then the transmitter makes a beeping sound.
5. Detect along the wire or at different points, start from the transmitter and slowly move to the load (accessories, lights, etc.) Pay attention to the position of the probe as mentioned above, when the sound signal (beep, beep sound) is normal, it indicates that the circuit is good, if the beep sound slows down or stops, it indicates that the probe head is either leaving the wire, or passing through the short circuit point.
6. If the detector is difficult or can not receive any signal, please adjust the position and angle of the detection, and then re-detect to see if there is a signal to be detected to the front and rear positions of the place where the detection is in doubt, if the leakage is found, the sound indication signal is normal only on the side of the circuit is good, and the other side of this position is abnormal.
7. The leakage point is at the place where the sound signal is terminated or changes suddenly. When the test is complete, turn off the detector and transmitter and disconnect from the circuit.
-
To measure the leakage of the line, whether the leakage of the live wire or the leakage of the neutral line. , it is necessary to disconnect all the electrical appliances of the socket. and turn off all lights.
After disconnecting the neutral wire from the power supply. Some of the zero lines are connected to the zero line row, and the zero line should be removed. A megohmmeter is then used to measure it.
If the value is lower than ohm, the leakage protector will act.
-
Summary. There are two ways to use a multimeter to measure whether the wire leaks from the ground: one is live measurement, the multimeter is adjusted to the AC file, and the voltage between the equipment shell and the ground is measured in the case of the equipment being energized.
This test is generally not recommended.
There are two ways to use a multimeter to measure whether the wire is leaking to the ground: one is the hidden species is live measurement, the multimeter is adjusted to the AC file, and the voltage between the equipment shell and the ground is measured in the case of the equipment being energized, and the voltage is generally induced by tens of volts, and the equipment can be determined to have leakage if it exceeds 100 volts. This method of detecting suspicion is generally not recommended.
The second method is to disconnect the power supply and measure the insulation resistance of the live wire and the neutral wire and the ground wire. If you use a multimeter to measure, generally the leakage is more serious can be displayed on the multimeter, and the resistance value is generally in the range of hundreds of ohms to tens of ohms. Digital Multimeter Measurement Method:
1. The multimeter is adjusted to AC gear, in the case of the equipment is energized, measure the voltage between the equipment shell and the ground wire (determined to be the ground wire), if the voltage range is tens of volts or 110 volts, it means that it is induction, if it is 220V or 380V, it means that it is leakage. 2. The multimeter is adjusted to the AC file, in the case of the equipment is energized, measure the voltage between the equipment shell and the neutral line, if the voltage range is tens of volts or 110 volts, it means that it is induction, if it is 220V or 380V, it means that the Heng Xuan macro is leakage. However, strictly speaking, the measurement of whether the circuit insulation resistance of the circuit leakage should use a shake meter, which is equivalent to a 1000V or 500V generator, and the leakage current passes through the sampling resistance inside the shake meter, and the sampling voltage indicator is generated on the resistance.
Normally, a stable greater than megaohm is qualified. The method is as follows: 1. Turn off the power of the equipment, fully discharge, do a good job of safety measures and hang reminder signs, and then untie the terminals on both sides of the cable to be tested.
The equipment is never allowed to be charged for measurement, so as to ensure the safety of people and equipment. 2. Before measuring, check whether the megohmmeter is in normal working condition, mainly check its "0" and "" two points. That is, shake the handle to make the motor reach the rated speed, the megohmmeter should be pointed to the "0" position when the short circuit is short, and the "" position should be in the "" position when the open circuit is open.
3. L" line end button is connected to the conductor of the equipment under test, "E" ground end button is grounded to the equipment shell, "G" shield is terminated to the insulating part of the equipment under test, and the meter is rotated at an average speed of 120 revolutions.
-
The methods for measuring leakage are as follows:
1. Power-off measurement method: turn off and disconnect all electrical appliances, use a multimeter 10k file, one meter pen receives or eliminates the fire line, and the other meter pen is grounded, if the resistance is not infinite, it is leakage;
2. Live measurement method: use the multimeter 250 volt AC voltage file to measure the metal shell of the electrical appliance suspected of leakage, one meter pen is connected to the shell, and the other meter pen is connected to the cavity of the ground, when the finger group sun needle shows that the voltage is higher than 30 volts, change to AC 50 volts, if the power supply is confirmed to be higher than 30 volts, it is leakage, and if it is lower than 30 volts, it is normal;
3. Live wire and neutral line measurement method: turn off and disconnect all electrical appliances, and measure the resistance between the live wire and the neutral line, which should not be infinity, but leakage.
-
Voltage regulators and resistors are used to supply precise current to the zero-sequence transformer, while the operating time is measured with a digital timer.
The main thing is to observe and remove the stitches. Generally, the DC short-circuit fault is more obvious, see which circuit of the DC screen is empty and trip, and then remove the line and lock the range according to the corresponding circuit one by one. The multi-point grounding of the DC system is not easy to check.
In the absence of an electric shock, the current of the leakage protector from the two wires in the power supply is the same at all times, in opposite directions. As a result, the magnetic flux in the primary coil disappears completely, and the secondary coil does not output.
-
Principle of electron pen test leakage:
The voltage tester is one of the tools often used by the majority of electricians to determine whether the object is charged or not. Its internal structure is a bulb with two electrodes, the bubble is filled with neon gas, commonly known as neon bubble, one pole of it is connected to the tip of the pen, and the other pole is connected to the other end of the pen after a high resistance in series. When the voltage between the two poles of the neon bubble reaches a certain value, a glow will be produced between the two poles, and the intensity of the glow is proportional to the voltage between the two poles.
When the charged body voltage to the ground is greater than the glow voltage at the beginning of the neon bubble, and when the tip of the pen of the voltage tester touches it, the other end is grounded through the human body, so the voltage tester will emit light. The function of the resistance in the voltage tester is to limit the current flowing through the body to avoid danger.
Principle of electron pen test leakage:
The voltage tester is one of the tools often used by the majority of electricians to determine whether the object is charged or not. Its internal structure is a bulb with two electrodes, the bubble is filled with neon gas, commonly known as neon bubble, one pole of it is connected to the tip of the pen, and the other pole is connected to the other end of the pen after a high resistance in series.
When the voltage between the two poles of the neon bubble reaches a certain value, a glow will be produced between the two poles, and the intensity of the glow is proportional to the voltage between the two poles. When the charged body voltage to the ground is greater than the glow voltage at the beginning of the neon bubble, and when the tip of the pen of the voltage tester touches it, the other end is grounded through the human body, so the voltage tester will emit light. The function of the resistance in the voltage tester is to limit the current flowing through the body to avoid danger.
-
"The method of detecting whether there is a vulnerability is as follows: Test electrical leakage: The easiest way is to use a voltage tester, it is better to use a multimeter, it can measure the voltage of leakage, and the method is:
If there is no ready-made ground wire, it can be connected to the water pipe, first hit the meter at the voltage level 250V, if it cannot be measured, gradually reduce it. This will let you know if there is a leakage.
-
It is composed according to the principle of magnetoelectric induction.
From electricity to magnetism, and from magnetism to electricity.
-
Introduction of leakage protector (1) Leakage protection: When the phase wire of the protected line is directly or through an unexpected load to the ground, and an approximate sinusoidal waveform is generated, and its effective value is a slowly changing residual current, when the current is greater than a certain value, the protector.
2.Working principle of leakage protector According to the working principle of the protector, it can be divided into three types: voltage type, pulse type and current type. The first two are currently available.
3.Classification of leakage protectors Classification of leakage protectors by function (1) Leakage relays. It only has the function of detection and judgment.
4.Leakage protector selection Leakage protector parameters (1) Rated leakage action current Under the specified conditions, the leakage is made.
-
1) Power-off measurement: turn off and disconnect all electrical appliances, use a multimeter RX10K file, one meter pen receives the fire wire, and the other meter pen is grounded (or faucet), the resistance should be shown infinity, otherwise the electricity leakage.
2) Live measurement: use the multimeter 250 volt AC voltage file, measure the metal shell of the electrical appliance suspected of leakage, one meter pen is connected to the shell, and the other meter pen is grounded (or faucet), when the pointer shows that the voltage is higher than 30-50 volts, switch to the AC 50 volt file, if the power supply is confirmed to be higher than 30 volts is leakage, and less than 30 volts is normal, and then the zero, fire power supply plug wire is adjusted and measured again to determine.
3) Leakage measurement between the live wire and the neutral wire (or between the live wire and the live wire): turn off and disconnect all electrical appliances, and measure the resistance between the live wire and the neutral wire, which should be infinite, otherwise it is leakage.
4) The accuracy of the above method to eliminate faults is convenient, fast and practical, and the megaohm special shake meter is only used when doing the project, and the use efficiency is low when maintenance, only the multimeter measurement is confirmed to be good, but the line does leakage, the shake meter is used, but the leakage can not be detected by the multimeter.
Cable leakage points can generally be detected by a leakage tester, but if you don't have this instrument at hand, you have to use a multimeter. >>>More
The break-step measurement can only measure the approximate length of the object to be measured, and the specific steps of the break-step measurement are as follows: >>>More
Method. 1. Directly measure the circumference of the circle, and then deduce it directly according to the circumference formula, that is: diameter = perimeter. >>>More
1) External method --- Figure A.
Ammeter. Are the voltmeter measurements current and voltage r? >>>More
There are many kinds of roughness testers, and the specific selection should be determined according to the size, material, and roughness value of your workpiece. >>>More