No, the chemical properties of lithium bromide solution are similar to salt, so feel free to put it!!
-
It is necessary to use a good plastic barrel, seal it well, lithium bromide has strong water absorption, pay attention to preservation, lithium bromide solution is highly corrosive, try not to store it for a long time.
The regeneration of lithium bromide solution should first sample and inspect the old solution, and then make a regeneration plan after analysis, and then do precipitation, filtration and other work on the old solution, all the regeneration working time is about 15-20 days, if the local conditions can meet the requirements (there is a larger site to store the solution, there is a storage tank, etc.) can be regenerated on site, but in the process of operation should be cautious and careful not to blindly process, otherwise it will cause extremely serious consequences.
Precautions for lithium bromide solution regeneration treatment:
1. The regeneration and treatment of lithium bromide solution has high technical requirements and should be carried out by a professional manufacturer with professional qualifications.
2. The solution should be tested and analyzed before and after the treatment work is carried out until the standard is reached.
3. In the process of processing, for the addition of some ingredients, (such as lithium hydroxide, lithium chromate, etc.)
-
Summary. Hello, happy to answer your questions.
It has strong corrosion on the ferrous metal of the unit. Corrosion of iron and copper in lithium bromide solution.
After the lithium bromide refrigeration unit is used for a long time, the leakage of the unit is caused by the vacuum management of the unit and unexpected circumstances.
Add lithium molybdate or lithium chromate solution (standard for unit solution content) Lithium molybdate and lithium chromate solution Characteristics: A protective film is formed on the steel plate inside the unit to prevent corrosion in the unit, and this item must be confirmed every year.
What kind of corrosion can be caused by lithium bromide leakage at high temperatures.
Please wait a minute.
Hello, happy to answer your questions. It produces strong corrosion code corrosion on the ferrous metal of the unit. Corrosion of iron and copper in lithium bromide solution.
After being used for a long time, the lithium bromide refrigeration unit will be leaked due to the vacuum management of the unit and unexpected circumstances. Lithium molybdate or lithium chromate solution (standard for unit solution content) Lithium molybdate and lithium chromate solution Characteristics: A protective film is formed on the steel plate inside the unit to prevent corrosion of the unit, and this item must be confirmed every year.
-
Store tightly sealed and store in a dry and cool place, not in contact with hydrogen and some live wave substances.
-
Try to achieve low temperature and vitrification sealing.