Generally speaking, the capacity of 1kVA can drive the left and right motors (and the power factor of the motor.
and reactive power compensation of transformers.
You can also calculate the rated current on the secondary side of a 2500kva transformer.
is 2500, so you can estimate how much load you can carry.
Rated load for long-term operation.
p=scosφ=
10% overload, transformer can last 180 minutes.
The transformer can last up to 150 minutes with a 20% overload.
The transformer can last up to 120 minutes with an overload of 30%.
Overload 60% transformer can last up to 45 minutes.
The transformer can last up to 15 minutes with an overload of 75%.
Overload 100% transformer lasts for minutes.
Overload 140% transformer can last for minutes.
Overload 200% transformer can last for minutes.
-
For example: transformer capacity 2500kva primary voltage 35kv, secondary voltage, transformer secondary rated current: i=2500 (
The secondary energy of the transformer is loaded with p=
-
Rated load for long-term operation.
p=scosφ=
The transformer can operate under short-term overload, more than 2000kw, as long as the temperature is not high, it can also operate for a certain period of time.
10% overload, transformer can last 180 minutes.
The transformer can last up to 150 minutes with a 20% overload.
The transformer can last up to 120 minutes with an overload of 30%.
Overload 60% transformer can last up to 45 minutes.
The transformer can last up to 15 minutes with an overload of 75%.
Overload 100% transformer lasts for minutes.
Overload 140% transformer can last for minutes.
Overload 200% transformer can last for minutes.
-
I'm not Mr. Guo, so let's take my point of view.
Generally speaking, the capacity of 1kva can drive the left and right motors (related to the power factor of the motor and the reactive power compensation of the transformer), you can also calculate by yourself, the secondary side of the 2500kva transformer is rated at 2500, so you can also estimate how much load it can carry.
-
Transformer power and motor calculations.
-
Transformer capacity and power are two different concepts. In this case, segments are needed to explain the relationship between them. 1.
Transformer capacityTransformer capacity refers to the maximum power that a transformer can output stably, usually expressed in kilovolt amperes (kVA). The size of the transformer capacity is related to the specification, structure and design of the transformer, which is one of the important factors to consider when selecting a transformer. 2.
Transformer powerTransformer power refers to the conversion relationship between the input and output power of the transformer, and ideally, its input and output power should be equal. The magnitude of the transformer power is related to the input voltage, output voltage, and current of the transformer. 3.
The relationship between transformer capacity and power There is a close relationship between the capacity and power of a transformer. Generally speaking, the larger the transformer capacity, the more power it can output stably. However, this is not always the case, as the actual power output of the transformer is also affected by many other factors, such as grid voltage conditions, load changes, ambient temperature, etc.
When selecting a transformer, it is necessary to determine the required capacity and power according to the actual demand, and comprehensively consider the quality, cost and reliability of the transformer to achieve the optimal choice.
-
Transformer capacity and power are two different concepts. Transformer capacity refers to the maximum capacity that a transformer can withstand, usually expressed in units VA (volt-ampere) or KVA (kilovolt-ampere). The capacity of the transformer depends on the connected load current and voltage level, and should generally be selected according to the actual value of the load current to meet the load requirements and the reliability and economy of the transformer operation.
The power of the transformer car voltage refers to the power that the transformer outputs or absorbs electrically, which is usually expressed in units of watts (W) or kilowatts (kW). The output power of a transformer is determined by the product of its input power and the efficiency of the transformer. It should be noted that the transformer capacity and power are not equal, generally speaking, the output power of the transformer is not equal to its capacity, and the actual output power is much smaller than the capacity, which is related to the efficiency of the transformer, the circuit connection method, etc.
-
1. According to the "Electric Power Engineering Design Manual".
The transformer capacity should be selected according to the calculated load, and the load rate of a single transformer with stable load power supply is generally about 85. i.e.: =s se where:
S - Xiang next to the calculation load capacity (kva); SE ——— transformer capacity (KVA); Load rate (usually 80 90).
2. Calculate the maximum power of each phase of the load: add the load power of phase A, phase B and phase C independently of each phase, such as the total power of phase A load is 10kW, the total power of phase B load is 9kW, and the total power of phase C load is 11kW, and the maximum value is 11kW. (Note:.)
The power of each device in the single phase is in accordance with the nameplate.
The maximum value above calculates that the power of a three-phase device is divided by 3, which is equal to the power of each phase of this device).
-
Summary. Transformer capacity refers to the maximum current that a transformer can hold in amperes (a). The power of a transformer refers to the maximum power that a transformer can provide, measured in watts (W).
Transformer capacity and power are related, generally speaking, the greater the transformer capacity, the greater the power. The power of a transformer is affected by its design parameters, such as the winding resistance value of the transformer, the coil voltage, the winding structure and materials, and the electromagnetic design. Transformer capacity and power are also affected by the operating temperature of the transformer and the ambient temperature.
Transformer capacity and power.
Transformer capacity refers to the maximum current that a transformer can hold in amperes (a). The power of a transformer refers to the maximum power that a transformer can provide, measured in watts (W). Transformer capacity and power are related, generally speaking, the greater the transformer capacity, the greater the power.
The power of a transformer is affected by its design parameters, such as the winding resistance value of the transformer, the coil voltage, the winding structure and materials, and the electromagnetic design. Transformer capacity and power are also affected by the operating temperature of the transformer and the ambient temperature.
Transformer capacity is typically measured in kilovolt-amperes (kVA) or kilowatts (kw). Power is the maximum power that a transformer is capable of accommodating and is usually measured in kilowatts (kW).
-
Hello dear, glad to answer for you. Transformer capacity refers to the maximum electrical load that a transformer can handle, and is often expressed in kilovolt-amperes (kVA) or the imperial unit kilowatt (kw). The larger the capacity, the greater the processing capacity of the transformer.
The capacity of a voltage transformer has the following relationship with power: capacity = input voltage x input current (unit: kva) and power refers to the efficiency of the transformer in converting electrical energy from input to output, which is usually expressed as "%".
There are two types of power losses in transformers: iron loss (core loss) and copper loss (coil loss). Iron loss refers to the energy lost by the working magnetic field of the transformer when connecting and switching, and the heat generated mainly affects the efficiency of the transformer, and the copper loss refers to the heat generated by the current generated by the energizing coil on its internal resistance, which increases the temperature of the transformer on the one hand, and reduces the transmission efficiency on the other hand.
The total power loss of the transformer can be calculated by the following formula: total power loss = iron loss + copper loss total power of the transformer = input power - total power loss total power = output voltage x output current (unit: kw) Therefore, we can calculate the power and power loss of the transformer according to its capacity and voltage.
-
Dear, I am glad to answer for you: the power of the transformer capacity calculation formula is determined by the load, i.e.: p2=u2ii2i+u2iii2ii+.
u2ni2in(va)p1=p2(va) where: the calculated secondary power of the P2 transformer, the calculated primary power of the P1 transformer, U2i and U2II....The voltage of each winding (V) of the transformer secondary stage, the value of which is determined by the load.
i2i and i2ii....The current of each winding (a) of the transformer secondary stage, the value of which is determined by the load. For the efficiency of the transformer capacity below 1kva transformer capacity is small, the efficiency is low, generally desirable = to, for the transformer capacity below 100va, choose the small value; The transformer capacity is between 100VA and 1000VA.
If the quality of the silicon steel sheet is poor, you can choose i1=p1 u1 (to where u1 is the primary voltage (v) to the empirical coefficient considering the no-load excitation current The transformer capacity can be calculated after the cross-sectional area of the silicon steel sheet core S and other parameters can be calculated.
It may be that a vortex has been generated.
For example, if an insulated wire is wound around an iron core, and after the alternating current is turned on, the current becomes a closed loop in the metal block. >>>More
Full-power step-up transformers and step-down transformers can be used interchangeably. If the transformer reaches full power, it will not cause damage, if the copper-clad aluminum wire or aluminum wire transformer cannot be used in this way, because the power of these two types of transformers is not as sufficient as the power of the all-copper wire transformer. >>>More
The isolation transformer is a safety power supply, which is generally used for machine repair and maintenance, and plays the role of protection, lightning protection and filtering. >>>More
The former operates at a higher frequency, resulting in a smaller number of coils and uses a ferrite core. >>>More
Formulas can be represented. The selection of transformer capacity and the type and characteristics of the load, the load rate, and the need. >>>More