Gree will automatically shut down the outdoor unit of a large air conditioner for how long it runs

Updated on technology 2024-04-08
23 answers
  1. Anonymous users2024-02-07

    Look at the temperature difference between indoor and outdoor, what is the temperature you set. It is difficult to shut down with a large 1p of 19 square meters, because the applicable area of the air conditioner of a large 1p is 12-18 square meters.

  2. Anonymous users2024-02-06

    It mainly depends on the temperature you set. If the space is large and the temperature setting is low, the boot time will be longer, and vice versa!

  3. Anonymous users2024-02-05

    Reasons why the outdoor unit of the air conditioner stops after running for a period of time:

    1. It is very likely that the compressor thermal protection of the air conditioner is shut down, and there are many reasons for the thermal protection of the compressor, such as poor ventilation of the outdoor unit, low fan speed or blade deformation and fracture, abnormal pipeline pressure, etc.

    2. If it is a newly installed air conditioner, it may also be caused by improper installation, and it should be returned or overhauled in time with the seller or after-sales service.

  4. Anonymous users2024-02-04

    According to the most reasonable data for you to control the temperature to calculate, more than 26 degrees during the day, more than 27 degrees at night, the temperature according to this regulation of the compressor may work at 50%-80%, because there is also an outdoor temperature situation. That is to say, the outdoor unit will work for 40-50 minutes per hour during the day and 30-40 minutes at night.

  5. Anonymous users2024-02-03

    This also refers to the heating of the room (day or night, and the heating of several sides of the room during the day); How much is the temperature difference between the set temperature and the actual temperature.

    The temperature difference is not large, and if the heat is small, it may automatically shut down within an hour, and vice versa.

  6. Anonymous users2024-02-02

    There are many reasons for the estimated thermal protection shutdown of the compressor, such as poor ventilation of the outdoor unit, low fan speed or blade deformation and fracture, abnormal pipeline pressure, etc. Should contact the seller or after-sales service in time for return or maintenance.

    The air conditioner crashes after one to twenty minutes of being turned on.

    The probable cause is the phenomenon of the compressor protection device tripping.

  7. Anonymous users2024-02-01

    If the machine itself is fault-free, it means that the indoor temperature reaches the set temperature, stop rotating to save energy, and start again after the temperature changes. If the machine is faulty, then the reasons are diverse, and the inspection can be confirmed

  8. Anonymous users2024-01-31

    1. During the defrosting period, the indoor air will be stopped. When the air conditioner runs for a period of time, the outdoor condenser will have a very thick frost and snow, if the frost and snow cannot be melted in time, it will directly affect the heating effect of the air conditioner, so when the air conditioner runs for more than 40 minutes to meet the defrosting conditions, the air conditioner begins to defrost.

    2. In the heating process of the air conditioner, the condenser of the outdoor unit is frosted, and the air conditioner enters the defrosting mode, at this time, the compressor will continue to run, the four-way valve is reversed, and the air conditioner is in the refrigeration state, at this time, the indoor fan does not rotate, because the cold air can not be blown out, and after the frost is removed outside, the four-way valve is re-reversed, and the air conditioner is turned back to heating.

    3. In this case, it may be that the compressor of the air conditioner is working abnormally or the amount of refrigerant in the system pipeline is insufficient.

    When the compressor works abnormally, the compressor will start and stop, the compressor will turn on and blow out hot air, and the compressor will stop and blow out cold air.

    4. In the case of insufficient amount of refrigerant in the system pipeline, the fan motor of the indoor unit is turned on, and the temperature of the coil drops quickly, which is hot air at the beginning and cold air at the back.

  9. Anonymous users2024-01-30

    That is short circuit protection or current overload protection, check whether the connection line of the indoor unit to the outdoor unit is damaged (generally a masterpiece of mice), if it is not to check the pressure protection switch, compressor capacitor, compressor. Do not go to the inspection as I said. You can definitely find out what is wrong.

    This is a message that appears when the set-top box's system is running incorrectly. Introduction: 1. This is the prompt information caused by the system operation error of the set-top box, such as the abnormal network connection of the set-top box, which causes some system functions of the set-top box to fail to operate normally; Or an error occurs when the system loads some underlying services, causing the loading to fail.

    2. The solution is as follows:1If this error message appears occasionally, the user can press the confirm button to turn off the prompt message and continue to use the set-top box normally.

    2.If the set-top box cannot be turned off after the prompt message appears, and the set-top box does not work properly, you need to shut down the set-top box and restart the set-top box to restore normal. 3.

    If the error message cannot be solved after restarting it several times, it may be caused by the system crash or hardware failure of the set-top box, and you need to contact the after-sales service of the set-top box, and arrange professional and technical personnel to flash the set-top box into the new system to solve the problem, or to detect and repair the hardware of the set-top box to solve the problem.

  10. Anonymous users2024-01-29

    What is the reason why the Gree air conditioner stops as soon as it starts? There is a reward for writing ccc vegetable chili ccc high-energy answerer2021-05-13Committed to becoming the person who knows the most to answer questions, consulting attention, becoming the 2523rd fan, taking Gree air conditioner as an example, the reasons why the air conditioner outdoor unit will stop after starting for a while are: 1. The compressor of the air conditioner is overheated to start self-protection, resulting in the external unit starting to stop for a while, and there are many reasons for the overheating protection of the compressor, such as poor ventilation of the outdoor unit, low fan speed or blade deformation and fracture, abnormal pipeline pressure, etc.

    2. The automatic mode may be turned on, when the set temperature is close to the room temperature, and the set temperature is reached, it will cause the machine to stop. It creates the illusion of failure when it is turned on and stops, but there is no problem with the actual air conditioner. 3. The voltage is abnormal or unstable, resulting in overcurrent protection of the compressor and causing shutdown.

    It is recommended to try a different voltage stabilizing device. 4. The temperature of the indoor coil is too high, resulting in protective shutdown. When the indoor temperature is 27 degrees Celsius and the outdoor temperature is above 20 degrees, the air conditioner cannot heat normally, which is easy to cause protection.

    5. The failure of the indoor fan causes no blowing, resulting in protection shutdown. If the outdoor fan fails, causing serious frosting, defrost is carried out, and the indoor air prevention function is entered. 6. The starting capacitor of the compressor is faulty, and after running for a period of time, the starting capacitor is faulty and short-circuited, causing the compressor to stop running.

    Questions. Inverter air conditioners do not have capacitors.

    Inverter air conditioners do not have capacitors. Well. Questions.

    The motherboard has also been replaced.

    The motherboard has also been replaced.

    The temperature sensor tube has also been replaced.

    The temperature sensor tube has also been replaced.

    Is the motherboard original?

    Questions. The compressor stops in less than 1 minute as the frequency increases.

    The compressor stops in less than 1 minute as the frequency increases.

    Original second-hand boards.

    Original second-hand boards.

    The problem of replacing two original second-hand boards is still.

    The problem of replacing two original second-hand boards is still.

    This has to be dealt with by a professional maintenance personnel.

    It may be that there is a problem with the accessories.

  11. Anonymous users2024-01-28

    Causes and elimination of high pressure and overheating:

    1. Too much refrigerant. Reduce the refrigeration dose appropriately.

    2. Poor heat dissipation. Check the condenser pipe for dirt and dirt and clean the condenser.

    3. The pipeline system is blocked. Refer to the pressure gauge to judge, eliminate, and re-process systematically.

    4. Dust and fouling of the evaporator or filter screen. The airflow becomes smaller, the system pressure and temperature are unstable, and the evaporator or filter is cleaned.

    5. Fluoride deficiency is also possible. When there is a lack of fluorine, the compressor discharge temperature will overheat, causing the overheating load protection switch to trip.

    The electrical problem is:

    1. Control circuit board failure.

    2. The temperature sensor is overloaded and the information is wrong.

    3. The power supply wiring is loose and the contact is poor.

    4. The starting capacitor or compressor starting coil is burned out.

    The information is insufficient, it can only be analyzed in this way, and there are many other possibilities, it is recommended to find a professional maintenance personnel to check it.

  12. Anonymous users2024-01-27

    There are many reasons, if it is a fixed-frequency air conditioner, there may be a problem with the starter, a problem with the starting capacitor will cause the external unit to start a direct shutdown protection, if it is a frequency conversion air conditioner, it may be a problem with the motherboard or power module.

  13. Anonymous users2024-01-26

    The probable cause is the phenomenon of the compressor protection device tripping.

    Compressor overload protection will trip, indicating that the system is too high-pressure, the pressure is too high, or the overheating current is too high.

    Check to see if there are a few of the following questions:

    The temperature of the outside unit of the air conditioner is too high, causing the air conditioner to enter protection mode. Check the heat dissipation of the air conditioner and whether the exhaust vent is blocked. Avoid direct sunlight.

    Thermistor failure, thermistor failure leads to temperature sensing failure of the internal unit, and the external unit cannot work normally.

    If the refrigerant is excessive or insufficient, it needs to be checked by a special master.

    The current and voltage of the air conditioner are unstable.

    Whether the external machine increases the air opening, and whether the empty opening is small.

  14. Anonymous users2024-01-25

    The air conditioner stops as soon as it starts, first check whether the starting capacitance of the outdoor unit is abnormal, secondly, check whether the power supply of the outdoor compressor is normal, and measure whether the temperature sensor of the outdoor unit is normal.

  15. Anonymous users2024-01-24

    The external unit of the air conditioner will stop as soon as it starts, as long as the internal unit is normally cooled, the external unit is a normal phenomenon. When the room temperature reaches a constant temperature, the compressor will no longer run and will be in standby mode. You can consult customer service for details, I hope to help you, I wish you a happy life!

  16. Anonymous users2024-01-23

    What is the reason why the Gree air conditioner stops as soon as it starts, according to the situation you said, it is generally a problem with the starting capacitor, and it is also possible that the compressor protector is bad.

  17. Anonymous users2024-01-22

    Gree air conditioner.

    This situation is the protection caused by the normal operation of the external machine, it is recommended to check the starting capacitor of the compressor first, if there is no problem with the capacitor, it is the problem of the compressor! Hope it helps!

  18. Anonymous users2024-01-21

    Problems with the computer board, or caused by insufficient voltage.

  19. Anonymous users2024-01-20

    Hello The reason why the Gree air conditioner will not stop is:1When there is a problem with the air outlet of the air conditioner, the outside of the air conditioner will also work non-stop.

    When the air conditioner is turned on, the greater the wind speed, the noise value of the air conditioner will naturally gradually increase, which is one of the reasons why the air conditioner does not stop running. 2.Loosening of the air conditioning panels.

    The air conditioner will also work non-stop. The vibration generated by the air conditioner during operation will cause the panels to rub against each other, resulting in the non-stop operation of the air conditioner. 3.

    The installation of the indoor unit of the air conditioner is incorrect or unstable, when the outdoor unit is running, the copper pipe is connected to the indoor unit, which leads to the influence of the compressor, and the outdoor unit of the air conditioner does not stop. 4.There is also a problem with the air conditioning compressor, which will also cause the air conditioner to accompany the rest of the machine non-stop.

    Hope the above helps you have a happy life! If you're happy with me, please give me a thumbs up (comment in the bottom left corner) Your gesture is very important to me, <>

  20. Anonymous users2024-01-19

    Dear, the problem you described can be caused by a variety of causes, and further examination and analysis are needed to determine the specific cause. The following are some of the reasons that may cause the external unit to shut down after ten minutes of turning on the Gree air conditioner:1

    Communication failure between the inside and outside units: Communication failures between the inside and outside units of the air conditioner may cause the outside unit to shut down. This can be caused by things like poor cable connection or damaged cables.

    2.Air Pressure Protection: If the air pressure of the air conditioning system is too high or too low, the system will automatically shut down to protect the equipment.

    This can be caused by a refrigerant leak or an internal malfunction in the air conditioning system. 3.Temperature Protection:

    If the temperature of the air conditioning system is too high, the system will automatically shut down to protect the equipment. This may be caused by an internal failure of the air conditioning system or an excessively high ambient temperature. 4.

    Power Problems: If the power supply to the air conditioning system is unstable or there is a problem with the power lines, the system may automatically shut down. If you are unable to determine the specific cause, it is recommended that you contact a professional aircon repairer for inspection and repair.

  21. Anonymous users2024-01-18

    This can happen if the refrigeration temperature is set at a high level, such as 30 degrees; The remote control is on the automatic, or the air volume is set on the force, which may also mislead the probe to misjudge the temperature, it is recommended to lower the temperature and try to see if this happens.

    Usually, household air conditioners are shut down and deactivated in September, and they are not turned on until May and June of the following year, and they are out of service for more than half a year. Therefore, before the air conditioner is turned on, a comprehensive "diagnosis" must be done to check whether there is a "problem" in the air conditioning equipment;

    According to the results of the inventory, under the guidance of professional and technical personnel, do a good job of maintenance and cleaning, this maintenance and cleaning should be in place, including the shell, body, and filter of the outdoor unit and the indoor unit, and then start the trial operation to observe the refrigeration speed and effect.

  22. Anonymous users2024-01-17

    If it will be stopped after a few minutes of real start-up operation, this is a normal phenomenon of fixed-frequency air conditioners. If the inverter air conditioner is shut down due to other faults, it will not start running automatically or stop immediately after starting, the most likely reason is the phenomenon of the compressor protection device tripping.

  23. Anonymous users2024-01-16

    This is normal.

    After the fixed-frequency air conditioner is turned on, the compressor (external unit) will automatically stop working when the indoor temperature reaches the set temperature; When the indoor temperature exceeds the set temperature, the compressor (external unit) will automatically start working.

Related questions
16 answers2024-04-08

It can be used, but the effect is not necessarily optimal. Because the specific design of each manufacturer is not exactly the same. It is difficult to match the internal and external units completely. After all, the standard is independent of each manufacturer, and if there are some problems, it is difficult to repair them after sales.

14 answers2024-04-08

The main difference between an air conditioner and a half horse is the input power and cooling capacity. >>>More

12 answers2024-04-08

When the refrigerant is filled into the refrigeration system from the cylinder, the cylinder can be connected to the repair valve, or the intermediate joint of the composite pressure gauge can be filled. Open the small cylinder and turn it upside down, exhaust the air in the tube, tighten the joint, fill the refrigerant, and close the straight-through valve when the gauge pressure does not exceed. Start the compressor to suck in the refrigerant, and at the same time observe the frost formation of the evaporator, and stop the filling when the evaporator is full of frost or condensation. >>>More

8 answers2024-04-08

The reason why the Gree air conditioner does not work. First: low voltage or aging lines. >>>More

18 answers2024-04-08

It is 295mm high, 834mm long, and 252mm thick, and there are differences in individual models, but the difference is not too big. The size of the air conditioner outside unit is different for different P, and the approximate size can refer to the small size of Gree Air Conditioner 1P776*540*320mm. >>>More