What is the expiration date of the foam solution in the fire foam system, and when is it replaced?

Updated on healthy 2024-02-09
10 answers
  1. Anonymous users2024-02-06

    Fire foam liquid can also be called water film-forming foam fire extinguishing agent, or light water foam fire extinguishing agent. Mainly composed of fluorocarbon surfactants.

    Fluorine-free surfactants (carbon-chloride surfactants or silicones.

    surfactants) and additives to improve foam properties (foam stabilizers, antifreeze, co-solvents and thickeners).

    etc.), and water composition. Everything has its own shelf life.

    And the shelf life of everything is also different. The same goes for firefighting foam fluids. How long is the fire foam liquid valid for? What happens when it expires?

    According to the national standard: GB15308 2006 "Foam Fire Extinguishing Agent".

    It is stipulated that the validity period of YE protein foam fire extinguishing agent and FP fluoroprotein foam fire extinguishing agent is 2 years, but if the storage environment is good, the validity period can be extended by 1 year; AFFF water-forming foam fire extinguishing agent, the state stipulates that the validity period is 8 years, if the storage environment is good, the validity period can be extended for 2 7 years. The national stipulation of SAR anti-soluble foam fire extinguishing agent is 2 years, and if the storage environment is good, the validity period can be extended by 1 year. g. The validity period of the national regulations for high multiple foam fire extinguishing agent is 2 years;

    According to the above national standards, we will find that in fact, the validity period of the fire foam liquid is value-added, so even if the fire foam liquid purchased by you is marked with 2 years or 8 years on the product instructions, if it is stored well, it may be extended to 3 years or 15 years.

    When the fire-fighting foam liquid expires, it can be judged whether it can be used after testing and testing according to the storage situation of the product, and do not rush to replace it. If the test confirms that the fire foam has expired, it should be replaced in time.

    To purchase fire-fighting foam liquid, you should go to a regular manufacturer, such as Xinxiao Fire Protection, which has been committed to the production and sales of foam fire extinguishing systems for many years, and is a trustworthy fire-fighting equipment. Factory.

  2. Anonymous users2024-02-05

    Only the water-forming foam liquid is valid for 8 years, and the rest are valid for 2 years.

  3. Anonymous users2024-02-04

    According to the relevant provisions of the current national standards, the storage validity period of the aqueous film-forming series is 8 years, and all anti-solvent types are 2 years, because after 2 years, the probability of the failure of the anti-solvent components is larger, 3 years for ordinary synthesis, 3 years for class A fire extinguishing agent, high and medium power fire extinguishing agent, 2 years for aqueous fire extinguishing agent and other fire extinguishers, and 2 years for protein and fluoroprotein series.

  4. Anonymous users2024-02-03

    According to the national fire safety code, ordinary foam fire extinguishers are valid for one year, and the agent must be replaced before they can continue to be used.

  5. Anonymous users2024-02-02

    The validity period of the aqueous film-forming foam is 8 years, and the other is basically two years. Shandong Qili Fire Production and Sales of Water Film-Forming Foam Liquid, Anti-soluble Water-Forming Foam Solution.

  6. Anonymous users2024-02-01

    2 years validity, mandatory replacement.

  7. Anonymous users2024-01-31

    1. The scrapping life of the fire extinguisher.

    Fire extinguishers must be scrapped if they reach the following years from the date of manufacture:

    Portable chemical foam fire extinguisher ——— 5 years;

    Portable acid and alkali fire extinguisher——— 5 years;

    Portable water fire extinguisher——— 6 years;

    Portable dry chemical fire extinguisher (gas cylinder type) - 8 years.

    Portable storage pressure dry powder fire extinguisher ——— 10 years;

    Portable fire extinguishers ——— 10 years;

    Portable CO2 fire extinguishers——— 12 years;

    Cart type chemical foam fire extinguisher ——— 8 years;

    Trolley type dry chemical fire extinguisher (gas cylinder type) - 10 years;

    Trolley storage type dry powder fire extinguisher ——— 12 years;

    Trolley fire extinguishers ——— 10 years;

    Cart type CO2 fire extinguisher ——— 12 years.

    2. Regardless of whether the fire extinguisher has been used or unused, it must be sent to the maintenance unit for hydrostatic test inspection when the specified period has reached the specified period from the date of delivery.

    1) Portable and cart-type fire extinguishers, portable and cart-type dry powder fire extinguishers, and portable and cart-type carbon dioxide fire extinguishers must be inspected after five years, and every two years thereafter.

    2) Portable and cart-type mechanical foam fire extinguishers, portable water fire extinguishers for three years, after every two years, must be carried out hydrostatic test inspection.

    3) Portable and cart-type chemical foam fire extinguishers and portable acid and alkali fire extinguishers must be tested and inspected for two years after the expiration of two years, and every other year thereafter.

  8. Anonymous users2024-01-30

    The validity period of water-based foam fire extinguishers has two aspects, namely the cylinder and the fire extinguishing agent.

    1. The signal cylinder of the water-based fire extinguisher:

    According to the relevant national regulations, the mandatory scrapping life of the first water-based fire extinguisher is six years.

    2. Fire extinguishing agent of the water old people-based fire extinguisher:

    When stored at normal ambient temperature, the validity period is two years, but generally speaking, the replacement period of the extinguishing agent is one to two years.

  9. Anonymous users2024-01-29

    For the use of fire extinguishers that have reached the following specified years, the building use management unit needs to send repairs to the fire extinguisher maintenance enterprise in batches:

    1) Portable and trolley water-based fire extinguishers have been shipped for 3 years, and every 1 year after the first maintenance.

    2) Portable and cart-type dry powder fire extinguishers, clean gas fire extinguishers, and carbon dioxide fire extinguishers have been manufactured for 5 years; Every 2 years after the first repair.

    The age of the fire extinguisher.

    If the factory time of portable and trolley fire extinguishers reaches or exceeds the following specified periods, they shall be scrapped:

    1) The water-based fire extinguisher has been in operation for 6 years.

    2) Dry powder fire extinguishers and clean gas fire extinguishers have been manufactured for 10 years.

    3) The carbon dioxide fire extinguisher has been in operation for 12 years.

    If the fire extinguisher has one of the following characteristics, it shall be scrapped:

    1) The cylinder is seriously corroded (the patent leather falls off in a large area, the rusted area is greater than one-third of the total area of the cylinder, and the surface is pitted) or the connection parts and the bottom of the cylinder are seriously corroded.

    2) The cylinder is obviously deformed and the mechanical damage is serious.

    3) There are defects such as cracks and no pressure relief mechanism in the head.

    4) The cylinder has an unreasonable structure such as a flat bottom.

    5) Portable fire extinguishers do not have intermittent jetting mechanisms.

    6) There is no name of the manufacturer and the date of manufacture (including the nameplate falling off, or the name of the manufacturer on the nameplate is blurred, or the date of manufacture is not recognizable).

    7) There are repair marks such as soldering, brazing or patching on the cylinder and head.

    8) Burned by fire.

  10. Anonymous users2024-01-28

    <> "Foam fire extinguishers are valid for several years.

    Fire extinguishers are a very common type of fire-fighting equipment, there are many types of fire extinguishers, but fire extinguishers also have a shelf life, so how many years is the validity period of foam fire extinguishers.

    Depending on the type of fire extinguisher, usually the validity period of portable foam fire extinguishers is 8 years, while the service life of pressure storage portable foam fire extinguishers can reach 10 years, and the cart type foam fire extinguishers are also 10 years, and the validity period of trolley storage pressure foam fire extinguishers is 12 years. The specific service life of these fire extinguishers should be determined according to the model and production date on the bottle body, and the fire extinguisher must be inspected once a year.

    What to pay attention to when using a fire extinguisher.

    1. When using fire extinguishers to extinguish fires, attention should be paid to the scope of application of different types of fire extinguishers. For example, foam fire extinguishers are suitable for extinguishing liquid fires, but not flammable and flammable water-soluble liquid fires; Carbon dioxide fire extinguishers are used to extinguish fires in precision equipment and documents, but not in potassium, magnesium, aluminum and other materials.

    2. The fire extinguisher hall also has a shelf life, for example, the effective time of carbon dioxide fire extinguishers is 12 years, the effective time of dry powder fire extinguishers is 10 years, and the validity period of water-based fire extinguishers is 6 years. Everyone should have their fire extinguishers checked and repaired regularly. According to the relevant regulations, water-based fire extinguishers are repaired for the first time 3 years after delivery, and every 1 year after the first repair.

    In addition, the fire extinguisher should be sent to the designated unit location after each use to check the performance of the fire extinguisher.

    3. Fire extinguishers should be stored in a dry, ventilated and easily accessible place. Under normal circumstances, the ambient temperature of the fire extinguisher should be in the range of minus 10-45 degrees, and it cannot be placed upside down, exposed to the sun, rain, etc. For example, the frost and sun protection measures must be taken every winter and summer to avoid the failure of carbonic decomposition.

Related questions
23 answers2024-02-09

Do you mean Ishamo's profile or her own?

23 answers2024-02-09

Classification of laundry detergent: 1. Ordinary laundry detergent and concentrated laundry detergent: ordinary laundry detergent has large and loose particles, good solubility, rich foam, but relatively weak detergency, not easy to rinse, and is generally suitable for hand washing; Concentrated laundry detergent, small particles, high density, less foam, but strong detergency (at least twice that of ordinary laundry detergent), generally suitable for machine washing. >>>More

9 answers2024-02-09

Japan's housing bubble is mainly due to the effect of Japan's contraction policy, but Japan's ** does not take the initiative to puncture the bubble.

13 answers2024-02-09

Solution: Right-click on the ** file (in window media format) and select "Run Mode". >>>More

19 answers2024-02-09

As long as the original software is not installed in the system disk (C drive), it is still there. But the registry was deleted after redoing the system, so those software may not be able to be used, but the general game software will not be affected, and it can still enter the game normally. >>>More