What size transformer is S11100?

Updated on technology 2024-04-26
9 answers
  1. Anonymous users2024-02-08

    1. Meaning of S11 series power transformer product model:

    1. S: Represents three-phase power transformer.

    Indicates the performance level code.

    100: indicates that the rated capacity of the transformer is 100kva

    3. S11-100 oil-immersed transformer working conditions:

    a. Normal environmental use conditions: the altitude does not exceed 1000m. Ambient temperature * high +40, * high daily average temperature +30, * high annual average temperature +20, outdoor * low temperature -25.

    b. Special environmental use conditions: more than 1000m above sea level. Ambient temperature is *high +40, *low -45. (specify at the time of ordering).

    4. Installation site: no corrosive gas, no obvious dirt environment.

    2. S11-100 oil-immersed transformer product implementation standard:

    1. IEC60076-1:1993 power transformer.

    2. Power transformer.

    3. GB6451-2008 technical parameters and requirements of oil-immersed power transformer.

    4. JB T10088-2004 6KV 500KV power transformer sound level.

  2. Anonymous users2024-02-07

    S11 is a transformer model, is there no letter after 100? That could be a 100kva transformer.

  3. Anonymous users2024-02-06

    S means three-phase, it is the loss level of the transformer, 10 is smaller than the loss of type 9, 11 is smaller than the loss of 10, and the loss of 11 is about 70% of 9.

    A transformer uses the principle of electromagnetic induction to change the AC voltage, and the main components are the primary coil, the secondary coil and the core (core).

    The main functions of the transformer: voltage conversion, current conversion, impedance.

    Transversion, virtual isolation, voltage regulation (magnetic saturation transformer) and other transformers.

    According to the use, it can be divided into: distribution transformer, fully sealed transformer, combined transformer, dry-type variable code voltage, oil-immersed transformer, single-phase transformer, electric furnace transformer, rectifier transformer, etc.

    The transformer converts the AC voltage and alternating current.

    and impedance of the device, when the primary coil is passed.

    When there is an alternating current, an alternating current is generated in the iron core (or core).

    Causes a voltage (or current) to be induced in the secondary coil.

    The transformer is composed of an iron core (or magnetic core) and a coil, the coil has two or more windings of Xunlu, of which the winding connected to the power supply is called the primary coil, and the rest of the windings are called secondary coils.

  4. Anonymous users2024-02-05

    Summary. Hello The capacity of this model transformer is 200 kVA, which can carry a power load with a maximum power of 200 kilowatts S11M200 10 model transformer, where "S11" means that it is a 10 thousand volt oil-immersed transformer specified by the Technical Committee for Standardization of Electric Power Industrialization, 200 means that the capacity level is 200 thousand volt ampere, and 10 means that the voltage level is 10 thousand volts.

    How many kilowatts can the transformer of the S11M200 10 carry.

    Hello The capacity of this type of transformer is 200 kVA, which can bear the power load with a maximum power of 200 kilowatts S11M200 10 model transformer, where "S11" means that it is a 10,000 kV oil-immersed transformer specified by the Technical Committee for Standardization of Electric Power Industrialization, and 200 means that the capacity level is 200 kVA, and 10 means that the voltage level is 10 kV.

    The capacity of a transformer refers to the size of the round object of active energy transmitted over a certain period of time, which is usually expressed in terms of kilovolt-ampere (kVA) orange liquid. The capacity application scenarios, use environment, load factors, etc. of the transformer are all related, and in the actual use, it is necessary to select and calculate according to specific conditions.

  5. Anonymous users2024-02-04

    S11-4000 10 transformer parameters.

    I will help you answer this question S11-4000 10 transformer closed with brother parameters Answer: The parameters of S11-4000 10 transformer are explained as follows:- S11:

    Indicates that the transformer is an oil-immersed tap-changer power transformer; - 4000: indicates that the rated capacity of the transformer is 4000kva; - 10: indicates that the rated voltage ratio of the transformer is 10kV.

    In addition to this, it is also necessary to know other parameters of the transformer in order to carry out detailed car attack analysis and design, such as: - no-load electric old bright current and no-load loss; - Short-circuit impedance and short-circuit loss; - Winding resistance and leakage impedance, etc. These parameters have a significant impact on the performance, efficiency and safety of the transformer.

  6. Anonymous users2024-02-03

    s11-250/10

    s stands for three phases.

    11. Indicates the code of the water product of the sexual distribution of the rent.

    250 indicates the rated capacity.

    10 indicates the rated voltage (high voltage).

    S11 is the magnitude of the national standard for transformer loss, which is lower than the loss of S9;

    10 is the rated voltage of 10 kV on the high voltage side, 400 volts on the low voltage side, and 800kVA is the rated capacity of 800kva.

    **This depends on what material you want to wind, more aluminum and less copper is much cheaper than all copper, and the impact of ** refers to the envy of the change and the requirements for the configuration of protective devices, insulation requirements, protection level, altitude, etc.

  7. Anonymous users2024-02-02

    Dear, hello, the weight of the manuscript transformer of S11800 is: 3 tons. S11800 dry-type transformer is a medium-sized transformer, which can be divided into a variety of specifications according to the capacity, the common specifications are 630kva, 800kva, 1000kva, 1250kva, 1600kva, 2000kva, 2500kva, 3150kva, etc.

    The weight of different specifications of the S11800 model transformer is different, between tons. 2.Capacity:

    630kva, 800kva, 1000kva, 1250kva, 1600kva, 2000kva, 2500kva, 3150kva, etc. 3.Input Voltage:

    10kv、。4.Output Voltage:

    400V, Rated frequency rate: 50Hz, Iron core breathing mode: natural cooling or forced air cooling.

    7.Insulation class: F or H class.

  8. Anonymous users2024-02-01

    How many tons does the s10-40000 10 transformer weigh.

    Hello, according to the model of S10-40000 10 transformer, its rated capacity is 40000 kVA, the rated voltage ratio is 10, it belongs to the large transformer. Its weight depends on factors such as the specific manufacturer, materials and design parameters. Generally speaking, the weight of the S10-40000 10 transformer should be more than 20 tons.

    S10-40000 10 transformer is a kind of high-voltage power equipment, which is mainly used in the power transmission and transformation process of the old trembling system to convert high-voltage power into low-voltage power to meet the electricity demand of different voltage levels. It has the characteristics of large size, heavy weight, high power, high efficiency and strong reliability, and is widely used in electric power, metallurgy, mining, chemical industry, rail transit and other fields. In addition to weight, the performance parameters of the S10-40000 10 transformer also include rated voltage, rated capacity, short-circuit impedance, loss, temperature rise, etc.

    During use, it is necessary to pay attention to the insulation performance, cooling method, operating environment and other factors of the transformer to ensure its normal operation and safe use. In a word, S10-40000 10 transformer is an important power equipment, its weight should be more than 20 tons, with a wide range of application fields and important roles.

  9. Anonymous users2024-01-31

    Summary. Hello dear! Thank you for your patience, according to the information given in the title, the rated capacity of the S10-40000 type 10 transformer is 40000 kVA, and the conversion ratio is 10, that is, the ratio of input voltage to output voltage is 10:

    1。The calculation of the weight of a transformer requires consideration of several factors, including the material and size of the transformer's core, coils, and other components, as well as additional equipment and oil levels. According to the provisions of the national standard GB T 6451-2015 "Technical Conditions for Transformers", the relative quality coefficient of S10-40000 type 10 transformer is, that is, the weight of the transformer is several times of its rated capacity.

    Therefore, the weight of the S10-40000 Type 10 transformer is about 138 tons (40000 .

    How many tons does the s10-40000 10 transformer weigh.

    Hello dear! Thank you for your patience, according to the information given by the topic, the rated capacity of S10-40000 10 transformer is 40000 kVA, and the conversion ratio is 10, that is, the ratio of input voltage to output voltage is 10:1.

    The calculation of the weight of a transformer requires consideration of several factors, including the material and size of the transformer's core, coils, and other components, as well as additional equipment and oil levels. According to the provisions of the national standard GB T 6451-2015 "Technical Conditions for Transformers", the relative quality of S10-40000 type 10 transformer is a combination factor, that is, the weight of the transformer is several times of its rated capacity. Therefore, the weight of the S10-40000 Type 10 transformer is about 138 tons (40000 .

    Generally speaking, the larger the conversion ratio, the more material and weight are required for components such as cores and coils of a transformer. At the same time, the larger the capacity of the transformer, the greater the number of wires and windings required to wind the coil, thus increasing its weight. 2.

    In addition to the weight of the transformer itself, it also needs to consider factors such as its additional equipment and oil volume. For example, the cooling system of the transformer, the disconnecting switch, the control equipment, etc., will increase its weight. The density of transformer oil is generally around 850 900 kilograms per cubic meter.

    Therefore, the amount of oil in the transformer also has an impact on its total weight. 3.The weight of the transformer is a problem that needs special attention during its transportation, transportation, transmission and installation.

    Due to the large size and heavy weight of the transformer, special equipment and measures are required for lifting and transportation to ensure its safety and reliability.

Related questions
5 answers2024-04-26

When the primary winding of the transformer is energized, the magnetic flux generated by the coil flows in the iron core, because the iron core itself is also a conductor, and the electric potential will be induced in the plane perpendicular to the magnetic field lines, and this electric potential will form a closed loop on the section of the iron core and generate a current, as if p a vortex is called "eddy current". This "eddy current" increases the loss of the transformer and increases the temperature rise of the transformer's core heating transformer. The loss caused by "eddy currents" is called "iron loss". >>>More

13 answers2024-04-26

The easiest way is to buy a ready-made control transformer, dismantle the secondary stage, and remember how many turns are used for how much voltage when dismantling, so that you can calculate how many turns the 5000V voltage should be around. If there are no special requirements, it can be made in the form of an autotransformer, so that the problems of interlayer insulation and lead wires can be simplified when designing the transformer. If there is an isolation requirement, between the primary and secondary pads around 3 layers of barley paper, and then around the secondary, pay attention to the enameled wire must be densely wound neatly, do not cross, do not go around to the very edge of the transformer skeleton, so as to prevent the coil from discharging the core, wrap a layer of pad around a layer of insulating paper, and wrap the outermost layer of 3 layers of insulating paper after winding, and then pre-dry, when the transformer wire package is not cool, soak in the prepared insulating paint, the insulating paint can not be too viscous, thin and easy to soak, Dry and then assemble the core. >>>More

11 answers2024-04-26

Generally speaking, the capacity of 1kVA can drive the left and right motors (and the power factor of the motor. >>>More

13 answers2024-04-26

The former operates at a higher frequency, resulting in a smaller number of coils and uses a ferrite core. >>>More

11 answers2024-04-26

To choose a 150kva transformer.

In line with the principle of "small capacity, dense distribution point", the distribution transformer should be located in the load center as far as possible, and the power supply radius should not exceed one kilometer. The load factor of the distribution transformer is the most efficient between, and the capacity of the transformer at this time is called the economic capacity. However, if the load is relatively stable, the transformer capacity can be selected according to the economic capacity in the case of continuous production. >>>More