What is the best way to brake the 3 phase motor 15KW, and the motor needs to be started frequently

Updated on technology 2024-05-25
9 answers
  1. Anonymous users2024-02-11

    Advantages of servo motor: 1. Accuracy: Closed-loop control of position, speed and torque is realized; Overcome the problem of stepper motor out-of-step; 2. Speed:

    Good high-speed performance, the general rated speed can reach 2 3 rpm; 3. Adaptability: strong anti-overload ability, can withstand three times the load of rated torque, and is especially suitable for occasions with instantaneous load fluctuations and requirements for fast starting; 4. Stable: Stable operation at low speed, and no stepping operation phenomenon similar to that of stepper motor will occur during low speed operation.

    It is suitable for occasions with high-speed response requirements; 5. Timeliness: The dynamic response time of motor acceleration and deceleration is short, generally within tens of milliseconds; 6. Comfort: Heat and noise are significantly reduced.

    Disadvantages of servo motors: Servo motors can be used in places where they can be attacked by water or oil droplets, but they are not completely waterproof or oil-proof. Hence ,...

  2. Anonymous users2024-02-10

    The brake of the motor is commonly used in energy consumption braking, reverse braking, mechanical electromagnetic brake braking, etc., 15kw power is larger, and energy consumption braking should be selected.

  3. Anonymous users2024-02-09

    Frequent start-up and frequent braking, it is recommended to choose a frequency converter and braking resistor. The accuracy is relatively high, which can protect the motor.

    If it is a motor of this type of frequent start motor (I use frequent start motor), and the braking accuracy is not high, the mechanical electromagnetic brake is used, which is the greater dynamic and static.

  4. Anonymous users2024-02-08

    Mechanical electromagnetic brake brake is the first choice!

  5. Anonymous users2024-02-07

    Mechanical electromagnetic brake.

  6. Anonymous users2024-02-06

    **Relatively inexpensive energy consumption braking.

  7. Anonymous users2024-02-05

    Hello, to this question, you need to know more about the application scenario you described. Basically, though, if you're going to use a transformer to brake a three-phase motor, typically, you'll need to choose a transformer with a rated capacity that is at least the same as the motor's rated capacity. For braking applications, you need to use a resistor that can absorb the kinetic energy of the motor and convert it into thermal energy.

    Such resistors usually require additional power to drive it, and a transformer is usually used to reduce the supply voltage to a suitable level. So, if you need to brake a three-phase motor with a roar and you need to use a transformer to drive the resistor, then you need to choose at least one transformer to make sure it can withstand the rated power of the motor. At the same time, you also need to make sure that the voltage rating and phase number of the transformer match the motor.

  8. Anonymous users2024-02-04

    Hello dear. For energy-consuming braking of three-phase motors, resistors or DC power can be used for braking. 1.

    If a resistor is used, it is necessary to calculate the required resistance value according to the rated power, voltage and current of the motor, and select the appropriate resistor for wiring starvation. If a DC power supply is used, a DC power supply with an output voltage and current that can meet the braking requirements is selected and wired. 2.

    In practice, transformers can also be used to control the braking of motors. Generally speaking, the three-phase power supply of the motor should be connected to the three-phase input end of the transformer, and the three-phase output end of the transformer should be connected to the three-phase winding of the motor. Then, a resistor or DC power supply is connected between the one-phase input and output of the transformer to control the braking effect of the motor.

    3.When selecting a transformer, it is necessary to calculate the required transformer capacity according to the rated power, voltage and current of the motor, and select a suitable transformer for wiring. Dear, thank you for your support, the above is my reply, I hope it can help you, I wish you a happy life

  9. Anonymous users2024-02-03

    The DC voltage required for DC braking of a 15kW motor depends on the specific brake model and hole potato specifications, and is generally indicated in the brake manual or the motor manufacturer's technical datasheet. Normally, the DC voltage required for the brake is a certain multiple of the rated voltage of the brake, which depends on the rotor inertia, braking time and braking torque of the motor.

    In practice, the DC voltage required for the brake is generally between 100V and 1000V, depending on the speed and load of the motor. If the motor speed is high or the load is large, a higher DC voltage needs to be provided for effective braking and shutdown.

    It should be noted that the current and voltage generated by the brake need to be controlled during DC braking to avoid overload or damage to the motor and brake. At the same time, it is also necessary to pay attention to the installation position and fixing method of the brake to ensure that it can effectively brake the motor during braking, and will not affect the normal operation and life of the motor. It is recommended to seek professional help and guidance during the installation and commissioning of the brake to ensure the reliability and safety of the braking system.

Related questions
10 answers2024-05-25

Contactors are made with 30A or 32A.

The current of the 15kw motor is generally less than 30A, and the specific value depends on the number of stages of the motor. You can choose 30A air opening, 32A for the two main contactors, 16A for the star point, 32A for the thermal relay, and the time relay is generally selected within 1 minute, and the setting time is about 10 seconds, depending on the load characteristics, and it is advisable to convert it to 2-3 seconds after the starting current is stable. >>>More

18 answers2024-05-25

The actual power of the motor depends on the load, not 3kw motor output power must be 3kw, if the no-load power is not large. >>>More

20 answers2024-05-25

First, the performance of the motor when it is out of phase. >>>More

8 answers2024-05-25

The output voltage of the single-phase inverter is three-phase 220V, that is, it is interchangeable, and if it is a single-phase 220V input, it is generally a triangle connection. It is suitable for the motor of 380V Y solution method to be changed to the connection method, and is generally suitable for motors below 3KW; >>>More

7 answers2024-05-25

Simple calculation: power*2=current; Each square copper wire has 3-6 currents (according to the length of the wire, the heat dissipation is good or bad). >>>More