The calculation of the amount of the grounding module, and the basis of the grounding module as the

Updated on technology 2024-02-09
6 answers
  1. Anonymous users2024-02-05

    According to the soil resistivity of the soil layer of the ground grid, the following formula is used to calculate the amount of grounding module:

    Horizontally embedded, single module ground resistance:

    rj = total ground resistance after paralleling: rnj = rj n where: soil resistivity (m).

    a, b length and width of the grounding module (m);

    rj Single module ground resistance ( ).

    RNJ Total Ground Resistance ( ).

    n Number of grounding modules;

    Module adjustment factor, generally taken.

  2. Anonymous users2024-02-04

    The economic dosage of the grounding module should depend on different soil quality, the laying thickness on the grounding body should be between 8-625px, according to the soil resistivity of the soil layer of the ground grid, the following formula is used to calculate the amount of grounding module (take AG M1 as an example):

    Horizontally embedded, single module ground resistance:

    rj?= Total ground resistance after parallel connection: rnj?=?rj?n where: —soil resistivity (m).

    a, b length and width of the grounding module (m);

    rj Single module ground resistance ( ).

    RNJ Total Ground Resistance ( ).

    n Number of grounding modules;

    Module adjustment factor, generally taken.

  3. Anonymous users2024-02-03

    The specific amount of grounding module can not give an accurate number, because each manufacturer produces different product resistance, so it can not be accurately determined, only you go to the specific manufacturer to consult.

  4. Anonymous users2024-02-02

    According to the soil resistivity of the ground grid site, the following formula is used to calculate the amount of grounding module:

    Single Ground Module Resistance: r=

    Total ground resistance after parallel connection: rm=r nη

    Soil resistivitym

    r Single ground module resistor

    rn ground resistance

    Number of grounding modules.

    Module adjustment factor.

    Number of modules: 4 6 10 20 40 60 100 adjustment factor.

    Compute instances. The calculation method of the grounding resistance with the grounding module as the grounding body is as follows:

    Single Ground Module Ground Resistance: r=

    Ground resistance after parallel connection: rm=r nη

    The soil resistivity is 300 m n: the number of grounding modules is 20:

    The adjustment factor of the module is taken as 0 65 Calculation result: rm=3 65 Note: Due to the uneven soil resistivity, the different design schemes, the use of auxiliary grounding materials and the influence of construction quality, the above calculation is only a theoretical calculation, and the actual effect may deviate from the theoretical value!

  5. Anonymous users2024-02-01

    Conductive resistance, conductive resistance in series or parallel.

  6. Anonymous users2024-01-31

    During lightning protection and grounding construction, quickly determine the number of vertical ground poles.

Related questions
12 answers2024-02-09

option explicit statement.

Used at the module level to force all variables in the module to be explicitly declared. >>>More

8 answers2024-02-09

The high-pressure chamber of the ammonia valve is connected to the cylinder, and the low-pressure chamber is the gas outlet and leads to the use system. The pressure gauge indicates the pressure of the gas stored in the cylinder. The outlet pressure of the low pressure gauge can be controlled by an adjusting screw. >>>More

7 answers2024-02-09

Moto E2 now! Around 1200 The current king of value for money. >>>More

4 answers2024-02-09

select * from log a,(select ,max(date) from logwhere id='10000' >>>More

14 answers2024-02-09

Yes! It's better to specify the IP! If the gateway is not set up, it will definitely not be able to connect to the network! >>>More