Acceptance of new houses. Floor heating pipe burst! Urgent, urgent... 5

Updated on amusement 2024-03-11
28 answers
  1. Anonymous users2024-02-06

    If the floor heating pipe is broken, even if it is a small pinhole, a floor heating pipe must be replaced as a whole, and it is not allowed to cut off and connect it, so that it can be used for a few years if it is good, and it is not good to say that it is not good

  2. Anonymous users2024-02-05

    This is unfounded, depending on what brand you use, generally good well-known brands are guaranteed for 50 years, there is a problem with the manufacturer directly compensation, you can't do this, in case there is a problem in the future, the cost of maintenance will be large, and there is a possibility of flooding Jinshan, their own home is a trivial matter, if it is flooded to others, hehe, you must be cautious, to choose a good pipe.

  3. Anonymous users2024-02-04

    No matter what brand you use, even if it is advertised that it has worked for 50 years, the treatment advice given to you is to connect the broken parts, and the house you buy belongs to the construction of the project and allows water leakage.

  4. Anonymous users2024-02-03

    Look at what brand of tube, there is no problem with the brand. The main thing is to look at the pipe, if it is hot melt when he is connected, there is generally no problem. If it is a mechanical connection, then hehe, it will definitely leak in a few years,,, the underfloor heating brought by the developer, and it is reasonable to keep it for two years.

  5. Anonymous users2024-02-02

    If it is caused by these two reasons, it can be connected in the second connection, if it is the cracking of the pipe or because the minimum wall thickness of the unilateral side does not meet the national standard, or it is not visible to the naked eye that there are quality problems, then it will be miserable, and the entire floor heating pipe must be replaced, otherwise the consequences will really be flooded. If it is the first category, you know what kind of pipe there are PE-XA pipes, as well as PE-RT pipes, these two pipes can be connected, but the connection method is different, don't make a mistake when connecting, it's no problem.

  6. Anonymous users2024-02-01

    It is better to use electric underfloor heating, once and for all.

  7. Anonymous users2024-01-31

    If the developer is responsible for the unified installation, he can only find the developer, and he can refuse to accept the house, or report to the quality supervision department.

  8. Anonymous users2024-01-30

    Of course, it is necessary to install it from the new one, find a home improvement company, it must be the best floor heating pipe problem, this buried project must use the first-class, reliable brand products.

  9. Anonymous users2024-01-29

    It must have been repaired by the developer.

  10. Anonymous users2024-01-28

    Upstairs is at their own expense.

    1. If the geothermal pipe is upstairs, you have to claim upstairs. If the upstairs geothermal pipe is within the warranty period, the upstairs will find the merchant to recover.

    2. If the geothermal pipe exceeds the warranty period, all losses must be borne by the upstairs.

    3. If the house is not well built, you can sue the developer.

    4. It is also possible to make a claim to the upstairs and the installation of geothermal pipes at the same time.

    Clean the filter once before using the floor heating pipe:

    Before using the floor heating system every year, the filter should be cleaned once a year, check whether the filter screen is damaged or blocked, and if there is damage, it needs to be replaced with a filter screen of the same specification, and dismantle it as it is.

    Floor heating pipes are cleaned once every 2-3 years:

    The floor heating system mainly adopts a specially designed pipeline circuit structure, the pipe shape is complex, the pipeline is long, the change of water supply temperature will produce calcium and magnesium ion scale, and there will be bacteria and algae in central heating, which will be attached to the inner wall of the pipeline for a long time, which will reduce the temperature of the floor heating system and cause failure.

  11. Anonymous users2024-01-27

    1. If the floor heating pipe bursts, then you are basically safe, and find a professional to confirm the cause of the pipe burst.

    2. Don't let the developer destroy the site. This is very important, there are generally two kinds of pipeline rupture, one is product quality, (if it is, then the manufacturer should be responsible, you are safe.) If it's during construction, workers work violently, or someone else breaks it, (you're safe, too.)

    But how bad it is, there must be a professional to judge, so call the police, why? Because you can't fight anyone, whether it's a developer or a former builder.

    3. How much do you want to bear? If you want this matter to settle down as soon as possible, then I will give you some suggestions, (provided that the developer puts the responsibility on you, and has already compensated for the losses downstairs) smash the ground --- restore the floor heating pipes--- strictly suppress --- confirm that there is no problem--- restore the ground --- OK.

    4. Let me briefly tell you about the normal construction process of floor heating: install pipes and water separators--- and then suppress - the purpose is to ensure the sealing of management--- if they are under normal construction, water leakage will be found in time.

    5. In short, solving the problem through normal channels is the most reliable, and if you compromise, your loss will be great.

    Also, no matter what tips he posted, it was all floating clouds, "If you give me a commodity, it will be bad when you give it to me, and it will be bad if you use it or not, the reason is too simple." 》

    In any case, the cause of the damage must be confirmed first.

  12. Anonymous users2024-01-26

    If the pipe is broken, the manufacturer is responsible, and if it is an operation error, it is responsible for yourself.

  13. Anonymous users2024-01-25

    If there is no leakage in the floor heating pipe when the inlet pipe is opened but the return pipe is not opened, it is not necessarily a problem of floor heating, and the leaking part should be opened in the presence of multiple personnel to find out the real reason, perhaps the problem of the hot and cold water pipe. In addition, there is no notice of the property to turn on the floor heating equipment, if the property notice can not be opened by itself, then the owner is also responsible. The first time you turn on the floor heating equipment, you usually need to be present with the property personnel, and you can only pass the pressure test after being pressurized.

    In any case, the cause of the damage must be confirmed first.

  14. Anonymous users2024-01-24

    Both the property and you are responsible, and the property also comes with compensation.

  15. Anonymous users2024-01-23

    The floor heating pipe bursts, and the hot water inside will shoot out directly, flooding the floor. We must regularly check the floor heating, my home in Huacheng heating An's floor heating, this is done very well, there will be a special housekeeper regular return visits, and I am not afraid that I always forget to clean or check.

  16. Anonymous users2024-01-22

    Because floor heating is a hidden engineering project, the completion acceptance can only start from the heating effect and whether there is leakage, so it is necessary to open the floor heating to know, it is best to use it for three consecutive days, so that the problem can be exposed.

  17. Anonymous users2024-01-21

    1. The main valve and each sub-valve are switched smoothly.

    2. A pressure test must be done, and the pressure lasts for one hour without significant blood pressure.

    3.Carefully inspect the floor row pipe for no excessive undulations, and if there are small cracks in the ground to be negligible.

  18. Anonymous users2024-01-20

    Hello answer, I hope to help you Intermediate acceptance and completion acceptance should be carried out, both of which have their own specifications and are indispensable. The intermediate acceptance of floor heating is from the laying of the insulation layer to the completion of the installation of the anti-heat medium collection and distribution device for the floor heating pipe, which is carried out by the construction unit and the relevant parties. Floor heating completion acceptance should be organized by the competent unit construction, supervision, construction and relevant units jointly carried out, acceptance needs to have construction drawings, design change documents, main materials, products and parts test reports, factory certificate, concealed engineering inspection records, intermediate inspection records, pressure test records, engineering quality inspection and evaluation records.

    The suppression link of floor heating acceptance.

    Precautions for Floor Heating Acceptance - Floor Heating Hydraulic Test Procedure.

    1.Before the hydrostatic test, safe and effective fixing and protection measures should be taken for the pressure test pipes and components, and the water pressure test pressure should be times of the working pressure, and the minimum should not be lower.

    2.During the hydrostatic test, the water is slowly filled through the water separator, and the air in the pipeline is discharged at the same time, and the water tightness is checked after it is filled with water.

    3.Slowly increase the pressure, the pressure rise time shall not be less than 5 minutes, after the pressure is boosted to the working pressure, the pressure is stabilized for 5 minutes, observe whether there is water leakage, and then make up the pressure to the specified test pressure, and the pressure drop within 10 minutes does not exceed the qualified.

    4.When carrying out hydrostatic experiments in winter, corresponding anti-freeze protection should be taken.

    Precautions for Floor Heating Acceptance - Floor Heating Pressure Test Procedure.

    1.Before the air pressure test, it is also necessary to take safe and effective fixing and protection measures for the pressure test pipes and components, and the pressure test pressure is times of the working pressure, and the minimum shall not be lower.

    2.An air compressor is used to gradually pressurize the water separator to check the air tightness.

    3.When the pressure is boosted to the working pressure, the pressure is stabilized for 5 minutes, and if there is no leakage, the pressure can continue to be supplemented to the experimental pressure, and the pressure drop does not exceed 5 minutes.

    The above are the precautions for floor heating acceptance. Whether it is intermediate acceptance or completion acceptance, it must meet the above requirements to ensure that there is no leakage of pipelines and components, flexible valve opening and tight closing, acceptance records, signing documents and archiving are also essential links.

  19. Anonymous users2024-01-19

    First of all, determine whether the water heating or electricity floor heating for home improvement is still there? The construction process of the two is different, and the detection is also different.

    1. Electric floor heating is generally to check the joint part and whether the heating is normal. 2. Plumbing is to be tested, such as the manifold situation, boiler efficiency, water pipe underground conduction and other such parts. Generally, as long as the temperature is tested to see if the temperature rises normally, the heat is normal, and the instrument is used normally.

  20. Anonymous users2024-01-18

    If it is a two-year warranty period, it is over the warranty period, because the warranty period for all building materials installation is calculated from the date of completion, so if it exceeds the completion time for more than 2 years, it is past the warranty period, even if you do not live in it.

    It is recommended to go to the merchant to see if it can be repaired, how much the repair cost is, and reduce losses.

  21. Anonymous users2024-01-17

    The warranty period should be calculated from the day the floor heating is installed.

    Because the house already belongs to you in 2012, as for whether you live in it or not, it is your business, because you are paying the property fee every month, and the property can only prove that you pay on time, and you have no way to prove that you are not living in it.

    This is the same as buying an appliance, if you buy a TV, you haven't used it for two years, and when you use it in the third year, it's broken, when do you say that the warranty period starts from?

  22. Anonymous users2024-01-16

    The shelf life is calculated from the time it was loaded.

  23. Anonymous users2024-01-15

    The specific method is: the low-temperature radiant heating system should be carried out intermediate acceptance and completion acceptance, and the intermediate acceptance of floor heating is from laying the insulation layer to the heating pipe laying and the installation of the heat-proof medium collection and distribution device is completed for pressure testing, which is carried out by the construction unit in conjunction with relevant parties.

    The completion and acceptance of floor heating shall be jointly carried out by the competent unit to organize the construction, supervision, construction and relevant units. Completion acceptance shall have construction drawings and design change documents, as well as test reports of main materials, products and parts, factory certificates and concealed engineering inspection records, intermediate inspection records, pressure test records, and engineering quality inspection and evaluation records.

    Before the hydrostatic test, safe and effective fixing and protection measures should be taken for the pressure test pipes and components, and the water pressure test pressure should be times of the working pressure, and the minimum should not be lower. Of course, I think it's more reliable to find a professional for acceptance.

  24. Anonymous users2024-01-14

    It is best to ask the professional inspection department to check, the general design is to go according to the specifications, the key is whether the materials used in the construction meet the design requirements, and the temperature of hot water should meet the requirements of floor heating, the temperature can not be too high (otherwise it is easy to scale), the floor heating pipe is generally made of a pipe coil ring, and the floor heating of the whole room has to be replaced, so it is best to ask the professional inspection department to check, you can consult the local quality inspection station planning bureau or construction bureau have this department.

  25. Anonymous users2024-01-13

    It is mainly to open the plug from the water collector, pressurize it with a water pressure pump, stabilize the pressure for 1 hour, the pressure drop is not less than, and the connections are not seepage or leakage.

  26. Anonymous users2024-01-12

    The burst of the water pipe depends on whether it is the responsibility of the developer during the warranty period, and it also depends on whether the water pipe itself is aging and bursting, or it is renovated or accidentally broken.

    1 Check to see if the power is turned off first, because water conducts electricity and is prone to danger, so turn off the power first. Then start to check how much water leaks after the water pipe bursts, which is generally directly related to the water pressure in the pipe. Whether the water is dripping or gushing out, the most important thing to do at this point is to close the valve of the water main immediately and report it to the local property department.

    2. Tie up the damaged part of the water pipe with special tape for repairing the water pipe.

    3. In addition, the cracks in the water pipe can also be repaired with glass fiber tape or ring gas resin adhesive.

    4 If the burst water pipe is severe, you can wrap the ruptured part of the water pipe with a towel, which can not only stop the water from spraying around, but also introduce the water flow into the placed bucket to avoid huge waste. At the same time, it can also close the valve of the main water pipe in the household, completely intercepting the tap water in the house**.

    5 If the cause of the burst water pipe is that the pipe is too old, you should find a plumber to check and repair it in time.

  27. Anonymous users2024-01-11

    Is your house hardcover?

    If so, then there is a development company that bears the relevant responsibilities such as maintenance and compensation;

    If not, if your house is not renovated, the indoor water pipe bursts due to non-human factors, and the construction unit will repair it;

    After the renovation, if the location of the water pipe burst belongs to the original construction unit installation and has not been altered, the construction unit will repair and compensate, if it is a changed place, the owner or the decoration company will deal with it by themselves.

  28. Anonymous users2024-01-10

    Three aspects, first, if the water pipe bursts before your acceptance, the developer will repair it free of charge!

    2. If you accept the decoration and move in, you can prove that the burst water pipe is not caused by you, and the house is still in the house, during the warranty period of the "Five Certificates and One Form", the problem is still the developer's, and the property has the obligation to help you deal with and coordinate.

    3. If the warranty period is exceeded, you will compensate yourself!

    Personally, it is recommended to carefully read the five certificates and one form you got when you received the house.

Related questions
15 answers2024-03-11

Generally speaking, there are three kinds - chemical soaking, projectile cleaning, and pulsed wave physical cleaning. Among them, the pulse cleaning method is the most used for floor heating, which can clean the scale and impurities of the floor heating pipe and water separator at one time. >>>More

7 answers2024-03-11

The laying of underfloor heating requires the following steps:1Determine how the underfloor heating will be arranged: >>>More

11 answers2024-03-11

Small apartments are suitable for installation. But the supervisor has to do the insulation. The main installation should be horizontal and vertical. >>>More

6 answers2024-03-11

The first is the acceptance of certificates: when the developer delivers the commercial house, it should show the buyer the "Record Registration Certificate for the Completion and Acceptance of the Commodity Housing", and the "Housing Quality Assurance Certificate", "Residential Instruction Manual" and the measured area report of the house must be provided to the buyer; If the above relevant information is not presented, the buyer may refuse to accept the house and complain to the construction administrative department. The second is on-site acceptance >>>More

13 answers2024-03-11

Methods of laying underfloor heating.

1. Installation method of dry floor heating. >>>More