What should I do if water enters the air conditioning pipeline? How to deal with leaking water pipes

Updated on home 2024-03-22
10 answers
  1. Anonymous users2024-02-07

    If only water enters the pipeline, the angle valve of the external unit is not opened, and the refrigerant is not discharged into the pipe. Then it's easier to deal with this way. Just use nitrogen to blow off the pipe, and then use a vacuum pump to vacuum to remove the water, the vacuum time is a little longer, and the water removal effect is better when the temperature of the pipeline is high.

    If the vacuum pressure can be maintained for a long time without rising, it means that the moisture is basically eliminated.

    If the refrigerant is mixed with moisture, or even the unit is already in operation (there may be water in the refrigeration oil), then it is troublesome to deal with. Put out the existing refrigerant, vacuum, add liquid, add filter drier to the pipeline of the system, run the system, let the refrigerant circulate, drive the water through the filter dried, and then replace the filter regularly, if there is more water, the refrigeration oil may deteriorate (emulsify), and the oil must be changed.

  2. Anonymous users2024-02-06

    Use the filter for cold storage (the one that can change the desiccant, do not use it) and string it between the high-pressure valve and the high-pressure pipe. Turn on the air conditioner. The compressor is sprayed with water to cool down.

    Collect fluoride for about 20 minutes at first. Change desiccant (color-changing silica gel). Work again for 1 hour and continue to change the desiccant until the desiccant does not change color.

  3. Anonymous users2024-02-05

    After rinsing the two devices with a higher nitrogen pressure, then increase the filter drier and fluoride for one hour. Change the silicone in the operation until no betting.

  4. Anonymous users2024-02-04

    # p' { q2 o2 @,a$ m% k- n% ?w c7 m) p$ {Clean the pipes with refrigerant. At least 500 yuan [not counting copper pipes]. Vacuum heating at the same time as heating the two devices.

  5. Anonymous users2024-02-03

    Materials: an air conditioner water pipe, screwdriver, knife, adhesive tape, waterproof tape.

    1. Generally, the pipeline of the air conditioner will be wrapped very well. So first of all, the thick tube wrapped around the white umbilical cord is removed.

    2. You can see the threaded pipe, which is the drainage pipe.

    3. Pull out this drain pipe from the joint.

    4. Connect the new tube as it was original, and it is best to wrap it with tape at the interface.

    5. If the broken place is very small, wrap it tightly with a little PVC waterproof tape.

    6. Wrap all the pipes and wires with tape according to the original appearance, and restore the installation.

    Precautions for daily use of air conditioners1. The shell of the indoor unit should be cleaned frequently, generally wiped clean with a clean dry cloth or wiped with neutral detergent, and it is absolutely not allowed to rinse directly with water.

    2. The indoor temperature should not be adjusted too low, otherwise it is not good for the human body, and the set temperature should be adjusted appropriately.

    3. If you feel that the indoor temperature is too high, you can reduce the set temperature appropriately.

    4. The effective use of the timer can achieve the effect of energy saving and comfort.

    5. There should be too many people in the air-conditioned room, too crowded, otherwise the cooling capacity will be insufficient, and the temperature will be difficult to drop.

    6. The doors and windows of the room should not be opened and closed frequently, and personnel should not enter and exit frequently, so as to avoid the loss of air conditioning.

    7. The glass window must be closed tightly and tightly, and double white curtains should be hung inside to reflect part of the light and heat penetrating through.

    8. The window can be opened briefly during indoor ventilation, and the window opening time is generally not more than 10 minutes.

    9. The air filter should be cleaned regularly, otherwise the airflow will be blocked, resulting in insufficient air volume.

  6. Anonymous users2024-02-02

    2.Clean up the leaky area: Clean the leaky area with a clean towel or water absorber to prevent water from flowing to the ground.

    3.Check the water pipe connections: Check if the water pipe connections are loose or broken. If so, you can try reconnecting or replacing the damaged part.

    4.Cleaning filters: Air conditioner filters can become clogged, causing clogged water pipes. Therefore, cleaning the filter may solve the problem.

    5.Contact a professional: If none of the above methods can solve the problem, it is recommended to contact a professional for inspection and repair.

  7. Anonymous users2024-02-01

    It may be that the insulation material on the air conditioning pipeline is too poor or too thin, and when the air conditioning refrigerant passes through, it will produce the physical phenomenon of condensation, and the pipe temperature material can be re-wrapped and wrapped with waterproof tape. It may be that the drain pipe of the air conditioner is aging or clogged, and the drain pipe can be replaced or unblocked.

    1. If the copper pipe leaks, you need to re-wrap the pipe temperature material and wrap it with waterproof tape. Moreover, when installing air conditioners, the air conditioning pipes are generally wrapped with thick insulation cotton on the head of the car, if the insulation cotton is damaged or the package is not tight, it will lead to water leakage.

    2. Check whether the outdoor unit pipe of the air conditioner is aging and deformed or blocked, if there is aging and deformation, you need to replace the new drainage pipe, you can replace the ordinary PVC pipe, if there is a blockage, you need to use a high-pressure water gun to dredge the blockage.

    3. When the air conditioner is installed, the height of the indoor unit should be higher than the height of the outdoor unit, which is conducive to the drainage of the air conditioner, and the installation must be firm. Therefore, it is necessary to calibrate the installation position of the spirit level.

  8. Anonymous users2024-01-31

    When there is a leakage of the indoor unit, you can carry out self-inspection according to the above situations, the most common is that the horizontal position of the indoor unit is displaced, you should carefully check whether the position is displaced, whether the pipeline lead end is high, if the horizontal position deviation is too large, the after-sales service department should be notified in time during the warranty period to overhaul and adjust. Those with strong hands-on ability can be adjusted by themselves.

  9. Anonymous users2024-01-30

    How to deal with air conditioning pipe leakage.

  10. Anonymous users2024-01-29

    If the air conditioner is installed and the test is normal, and the water leakage occurs after a few days, it may be that the air conditioner drain pipe is not evenly inclined when it is installed. Next, let's take a look at how to solve the leakage of the indoor unit of the air conditioner, whether the leakage of the indoor unit of the air conditioner can still be used, and how to deal with the leakage of the air conditioner inside, I hope it can help you. 1. How to solve the leakage of the indoor unit of the air conditioner 1. The leakage of the indoor unit of the air conditioner may be caused by the displacement of the horizontal position of the indoor unit of the air conditioner, you can first remove the indoor unit of the air conditioner, pull the bottom of the indoor unit outward by hand, and hold it up as a whole until it is detached from the hook of the fixed hanging plate, and remove the indoor unit and put it on the ground.

    2. Use a spirit level to check whether the fixing plate is loose or tilted, and then adjust the tightness of the screws according to the actual situation to ensure the levelness of the fixing plate. 3. Check the deformation and sag of the hook, you need to adjust and correct it with a hammer or pliers, and then wrap a few thermoplastic belts or ordinary plastic gods on the hook according to the horizontal height to pad the height, so that the two hooks maintain a consistent level, and after the adjustment, you can hang the indoor unit on it. 2. Can the air conditioner indoor unit leak continue to be used 1, the air conditioner indoor unit leakage can not continue to be used, if the air conditioner is installed after the test is normal, and the water leakage occurs after a few days, it may be that the air conditioning drainage pipe is not evenly inclined when it is installed, and the rear end of the drainage pipe is higher than the front, so that there is a water phenomenon in the middle of the drainage pipe.

    2. After the air conditioner is used, the condensate is collected in the middle of the drain pipe to form a pocket of water to produce air to increase the drainage pressure, and the condensate flows through the drain pipe leakage place when the next machine is cooled, because the air conditioner has no pressure to drain the condensate from the drain pipe normally, it will cause the air conditioner to leak. 3. You can use the PPR drainage pipe, and the installation requires a certain flow degree, and it cannot be a place where the drainage pipe has water, if the drainage pipe is very long, the exhaust hole should be installed at the place where the drainage pipe is 4 6 meters. 3. How to deal with the leakage of the air conditioner 1. Under normal circumstances, the condensate of the air conditioner should be generated on the evaporator, so that the condensate will flow along the evaporator to the water collection tray, and the filter screen is installed outside the evaporator, which is used to prevent dust from polluting the evaporator and affecting the refrigeration effect, but if the filter screen is dirty, the dust on the filter screen will block the water vapor, so that the condensate will be generated on the filter screen, and the condensate on the filter screen will have nowhere to go, and there will be water leakage.

    2. At this time, the user can remove the filter in the air conditioner by himself, and then clean it, which can solve the problem of water leakage of the air conditioner.

Related questions
12 answers2024-03-22

It's not that inverter air conditioners are like this, and the two Midea inverter air conditioners in my room at home don't have this problem!! The air conditioner in my hometown was damaged a few days ago, and then someone replaced the pipe and added cold silence, and there was a sound when it was turned on, and the noise was quite loud! It's like a lonely and flowing voice in the tube! >>>More

15 answers2024-03-22

Completely disconnect the power of the air conditioner, open the electric control cover to check the status of the internal electronic control components and the fan motor, or report to the air conditioner manufacturer for after-sales repair. The indoor unit of the air conditioner is designed for waterproof structure according to the electrical appliances used indoors, and the waterproof performance of the indoor unit itself is very poor, and if there is external water, it is easy to cause water damage to the electronic control parts of the indoor unit of the air conditioner, the fan motor and other key components. When the indoor unit of the air conditioner is not properly flooded, the treatment method: >>>More