Why does the steam boiler keep showing ultra high water level and often alarming?

Updated on society 2024-03-06
11 answers
  1. Anonymous users2024-02-06

    Why does the steam boiler keep showing ultra-high water level and often alarming? Common causes of alarms in the case of high water level in steam boilers:

    1. Electrode column corrosion.

    2. The wire is broken.

    3. The circuit board of the alarm box is damaged.

    4. The alarm horn is broken.

    5. The alarm is turned off.

    Please rule out from easy to difficult. One is to check the circuit of the water level alarm, and the other is to check the water level alarm steam and water connection pipe to see if the water impurities cause the alarm to work abnormally.

    Electric steam generator - look for Altai, multi-specification spot can be customized.

    Altai electric steam generator manufacturers have been focusing on the field of electric heating, with strong reserve resources and rich practical experience. Electric steam generators are available in stock for multiple specifications, and can be customized.

    Yancheng Altai environmental protection equipment **** advertisement.

    The electric steam generator has fast gas output, large gas volume, and the temperature can reach 171 20 years of quality factory direct sales.

    Best steam generator, specializing in the production of all kinds of steam generators, complete variety, can be customized according to demand, simple operation, one-stop after-sales service, no need to report for inspection, so that you can use it with peace of mind.

    The high water level of the boiler alarmed, how to deal with it, kept alarming, and I didn't understand how to help look at it.

    After the high water level alarm, look at what the actual water level is, look at the plate level gauge, if the actual water level is not high water level, if it is, put part of the boiler water away, until the middle water level, if the flat level gauge water level is normal, that is, the water level alarm is faulty, and it can be repaired.

  2. Anonymous users2024-02-05

    If the steam boiler has been showing ultra-high water level, the alarm often indicates that the water level is relatively high, and the water level can be adjusted a little lower to see its overall response.

  3. Anonymous users2024-02-04

    If the water level is high, an alarm will be displayed, and you can lower the water level and test whether there is a problem with the equipment.

  4. Anonymous users2024-02-03

    Be sure to pay attention to safety in the steam cooker, and if there is too much water, you can let it go a little.

  5. Anonymous users2024-02-02

    Call someone to repair the water level limiter, is it broken?

  6. Anonymous users2024-02-01

    When the boiler water level is normal, there is always a low water level alarm, which may be caused by the failure of the boiler water level transmitter or the improper adjustment of the water level switch.

    1. Transmitter failure: first check whether the transmitter is working normally, if the transmitter power supply is off, there will be a false alarm; An alarm will also appear if the transmitter line is in poor contact.

    2. Improper adjustment of the water level switch: check the water level switch to determine whether the value of the ruler is reasonable, and it is recommended to adjust the adjustment value of the water level switch to the minimum water level during normal operation to avoid low water level alarm.

    3. Blockage of the sewage outlet: check whether the sewage outlet is blocked, if the sewage outlet is blocked in front of the plug, the boiler water level is not easy to decrease, and it is easy to have a low water level alarm.

    In short, there are many reasons for the normal boiler water level and always low water level alarm, and it is necessary to comprehensively check whether the components of each system are working normally, and combine them with investigation according to the situation, so as to find out the actual cause of the problem and avoid unnecessary losses.

  7. Anonymous users2024-01-31

    The boiler water level is normal, what is the alarm of always low water level?

    Hello dear, the boiler water level is normal, what is the alarm of always low water level? Visually the water level of the boiler is in a normal state, but the low water level alarm is always low, indicating that there is a problem with the water level control system of the boiler, which needs to be carefully overhauled to eliminate the hidden dangers of the safe operation of the boiler. (1) If the water level is normal, it means that the water level control alarm has been damaged, and the output line behind the water level alarm can be temporarily connected together (shorted), note:

    Don't make the mistake of short-circuiting the input power of the alarm! This allows the boiler to be started normally (the level gauge can be replaced later). (2) If the liquid level is really low, you can increase the water pressure to solve it, and check whether the water valve is damaged by the core, which will also cause the boiler to be too slow

    When the liquid level is low, the output wiring of the liquid level controller must not be shorted, and the consequences of forced furnace opening are unimaginable! It should be that there is a lot of water loss, and it is necessary to replenish water as soon as possible to eliminate the defect of open meditation hunger. I hope mine can help you.

    If my answer is helpful to you, please give a thumbs up (comment in the lower left corner), look forward to your like, your efforts are very important to me, and your support is also the motivation for my progress. Finally, I wish you good health and a good mood!

  8. Anonymous users2024-01-30

    Dear, hello, the electric boiler water level alarm has the following points: 1) The water seepage is not smooth, and the scaling of the water storage tank is more serious: check the fence net of the water valve and remove the debris; Clean the water tank and remove the oil.

    2) Fouling or destruction of the water line probe: Clean the water line probe shed or replace it. 3) The steam pipe is reed with traces of more than 70-90 degrees of heating pipes, and after a long time, the plastic of the chain socks layer is closed to block the steam outlet, and the valve is relieved of pressure alarm:

    Replace the steam pipe with a stainless steel bellows. 4) The temperature camera cable is damaged or bitten off by mice, and the control panel cannot check the temperature alarm. 5) The control panel is destroyed, and the common faults of single-chip microcomputer programming:

    Replace the control panel.

  9. Anonymous users2024-01-29

    Summary. Electric boilers work all the time but don't heat up? 1. Burning of heating tubes.

    Solution: Replace the heating tube with a new one; 2. The temperature sensor is out of order, and there is no signal command to the control system. Solution: Replace the sensor probe; 3. The AC contactor does not move.

    What is going on if the electric boiler is not hot, the heating of the electric boiler is not hot, and the heat dissipation system of the electric boiler is not hot as a whole. First of all, ensure that the electric boiler is in normal operation mode. You can touch whether the water outlet of the electric boiler is hot, if the water outlet of the electric boiler is not hot, it proves that the electric boiler is not hot.

    What is the reason why the temperature of the electric boiler room cannot be raised if it is not hot, such as the insufficient feed water pressure to make up for the inlet water level gauge and the false water level appears; The leakage caused by the loose blowdown valve of the electric boiler can cause the lack of water in the electric boiler. It should be noted that the cause of water shortage in electric boilers should be found in time and dealt with correctly.

    The electric boiler displays the water level alarm, and the work does not heat up.

    Electric boilers work all the time but don't heat up? 1. Burning of heating tubes. Cavity Mitigation Solution:

    Replace the new Wu moldless heating tube; 2. The temperature sensor is out of order, and there is no signal command to the control system. Solution: Replace the sensor probe; 3. The AC contactor does not move. What is going on if the electric boiler is not hot, the heating of the electric boiler is not hot, and the heat dissipation system of the electric boiler is not hot as a whole.

    First of all, ensure that the electric boiler is in normal operation mode. You can touch whether the water outlet of the electric boiler is hot, if the water outlet of the electric boiler is not hot, it proves that the electric boiler is not hot. The electric boiler room is not hot, the temperature cannot be raised, and the reason is found, such as insufficient feed water pressure to make up for the inlet water inlet water level and false water level due to incorrect water level indication; The leakage caused by the loose blowdown valve of the electric boiler can cause the lack of water in the electric boiler.

    It should be noted that the cause of water shortage in electric boilers should be found in time and dealt with correctly.

    1) If the water level is normal, it means that the water level control alarm has been damaged, and the output line behind the water level alarm can be temporarily connected together for the first time (shorted), note: do not mistakenly short-circuit the input power supply of the alarm draft! This allows the boiler to be started normally (the level gauge can be replaced later).

    2) If the liquid level is really low, you can increase the water pressure to solve, and at the same time check whether the water valve is damaged by the core, which will also cause the boiler to be too slow, and the alarm can be opened normally after solving all the problems. It should be that there is a lot of water loss, and it is necessary to replenish water as soon as possible to eliminate the defect.

  10. Anonymous users2024-01-28

    Summary. Dear, hello, first observe whether the water level gauge on both sides of the boiler is consistent, if it is inconsistent, this phenomenon may be blocked by the water level gauge, the water level gauge on both sides must be flushed, if the water level gauge can not change the situation after flushing, then it is possible that the water level alarm system is faulty, the furnace must be stopped urgently, and ask the electrician to repair it quickly. The water level display system is an important guarantee for the safety of the boiler, and problems must be repaired in time.

    The boiler water level is normal, what is the alarm of always low water level?

    If it is inconsistent, Liang guesses that this phenomenon may be blocked by the water level gauge, and the water level gauge on both sides must be flushed, if the water level gauge can not be changed after flushing the water level gauge, then it is possible that the water level alarm system has a soak type barrier, and the furnace must be stopped urgently, and the electrician must be repaired quickly. The water level display system is an important guarantee for the safety of the boiler, and problems must be repaired in time.

    1) If the water level is normal, it means that the water level control hail alarm has been damaged, you can temporarily connect the output line behind the water level alarm together (short circuit), note: do not short circuit the input power supply of the alarm by mistake! In this way, the boiler can be started normally (the liquid level can be replaced in standby later).

    2) If the liquid level is indeed low, you can increase the water pressure to solve, and check whether the water valve is damaged by the core, which will also lead to the water on the pot furnace is too slow, and the alarm can be opened normally after solving all the problems, note: when the liquid level is low, the output wiring of the liquid level controller must not be shorted, and the consequences of forced furnace opening are unimaginable! It should be that there is a lot of water loss, and it is necessary to replenish water as soon as possible to eliminate the defect.

  11. Anonymous users2024-01-27

    The boiler water level is normal, what is the alarm of always low water level?

    Hello dear, I will answer for you this time, please be patient. <>

    1) If the water level is normal, the water level control alarm has been damaged, you can temporarily connect the output line behind the water level alarm together (short circuit), note: do not short circuit the input power supply of the alarm by mistake! This allows the boiler to be started normally (the level gauge can be replaced later).

    2) If the liquid level is really low, you can increase the water pressure to solve, and check whether the water valve is damaged by the core, which will also cause the boiler to be too slow. It should be that there is a lot of water loss, and it is necessary to replenish water as soon as possible to eliminate the defect.

Related questions
15 answers2024-03-06

Indicates that the rated evaporation capacity is.

That is, the boiler produces steam per hour. >>>More

8 answers2024-03-06

Low self-esteem causes such feelings.

Staring into someone's eyes for a little longer makes it feel unnatural and uncomfortable. >>>More

15 answers2024-03-06

The cause of the dry cough may be allergic, and after the cough center is excited, it keeps coughing and can't stop.

6 answers2024-03-06

If the third screen you mentioned appears, you usually choose the last normal start. >>>More

23 answers2024-03-06

may be because his appearance is really bad, and the protagonist is often the righteous party, Zhang Yaoyang became popular with "Prison Storm", this film makes his villain image too deeply rooted in the hearts of the people. >>>More