ABB ACS800 inverter, now report 7110 fault, solve

Updated on technology 2024-02-08
11 answers
  1. Anonymous users2024-02-05

    First of all, the encoder problem will indeed cause the fault you mentioned, the key is to reduce the vibration of the motor to the encoder, but also to check whether the connecting shaft between the encoder and the motor is straight (preferably with a soft connection), check the wiring to avoid interference problems.

    Because the encoder will cause the DC bus voltage to fluctuate, you had better use the drivewindow to monitor the DC voltage curve to see clearly. The voltage fluctuation of the DC bus will make the inverter think that the excess energy of the DC bus is caused by the insufficient braking resistance and braking ability, so it reports 7110. The 3220 undervoltage is also for the same reason.

    Secondly, the overvoltage control (overvoltage ctrl) must be set to off, the undervoltage control (undervoltage ctrl) can be set to on, and in addition, it must be sure that the connection between the brake chopper and the brake resistor is correct and reliable.

    There is also a replacement RTAC board to try.

    If you are sure that none of the above problems are available, then you should consider whether the ABRC work of the brake chopper control board is unstable, and it is recommended to contact ABB4S** or ABB after-sales service to help you replace the ABRC control board. Welcome.

  2. Anonymous users2024-02-04

    Try setting the upper and lower limits of the encoder feedback again.

  3. Anonymous users2024-02-03

    Could it be signal interference?

  4. Anonymous users2024-02-02

    Recalibrate the encoder parameters, if the feedback is not normal, it is equivalent to a flying car, and the braking unit will definitely be put into work.

  5. Anonymous users2024-02-01

    ACS800 inverter report 2310 is an overcurrent fault, check whether the motor cable is damaged, whether the motor does not rotate, 2310 and the inverter have little to do with it, basically it must be a problem with the motor and cable.

    ABB inverter ACS800 fault 2310 handling method:

    Check the load, motor current, and mechanical parts of the system;

    If an output contactor is used, the modulation of the inverter should be stopped first, and then the contactor should be disconnected;

    Check the motor voltage and connection method on the motor nameplate, and compare it with 99 sets of parameters;

    ramp times that are so short that the overflow controller does not have enough control time, check the load and increase the ramp time;

    the speed or torque oscillation of the motor, caused by the given speed to check whether the given value of the speed oscillates, caused by the given torque to check whether the given torque oscillates, caused by the overcompensation of the speed response to check the parameter setting of the speed regulator, caused by the wrong pulse encoder value to check the waveform of the pulse encoder and check the number of pulses, caused by the motor model, to obtain the correct motor data from the motor nameplate and to compare 99 sets of parameters;

    Check the insulation of the motor and motor cable, break the connection between the motor cable and the inverter, run the inverter in scalar mode, if the inverter does not trip, it means that the inverter is good;

    inspect and measure motors and motor cables with a high-resistance meter or an insulating meter;

    Check whether the rated current value of the motor is located, and check the output current, torque and limit word;

    Confirm that there are no power factor correction capacitors and surge absorbers on the motor cables;

    Check the pulse encoder, pulse encoder wiring (including phase sequence) and XTAC module;

    Check and correct the motor data according to the motor nameplate;

    Inspect and replace optical fibers, inspect flat cables, inspect and replace current transformers, check output current, torque, and limit words;

    Inspect and replace the current sensor, replace the XINT board, confirm that the flat cable is connected correctly, and replace all fibers between the INTS board and the XPBU board.

  6. Anonymous users2024-01-31

    Causes: 1. The sensor pins are loose or in poor contact.

    Solution: Adjust the prong position to service the sensor.

    2. The transmission blind sensor is damaged, and the resistance value is wrong.

    Solution: Replace the sensor.

    3. The control circuit board is faulty, and the control signal cannot be received and sent.

    Solution: Replace the control circuit board.

  7. Anonymous users2024-01-30

    Summary. Hello, glad to answer for you. comm module(7510).

    aw 1 bit 12

    Programmable fail-safe function due to periodic loss of communication between the drive unit and the main engine.

    Solution: Check the communication status of the fieldbus. Refer to the chapter Fieldbus Control, or the Fieldbus Adapter manual.

    Check the parameter settings:

    Group 51 COMM Module Data (for fieldbus adapters).

    Group 52 Standard Modbus (for standard Modbus bus links).

    Check the fault function parameters.

    Check the cable connections.

    Check whether the host is able to communicate.

    ABB ACS800 inverter reported 7510 what is the reason?

    Hello, glad to answer for you. comm module(7510).

    aw 1 bit 12

    Programmable fail-safe function due to periodic loss of communication between the drive unit and the main engine.

    Solution: Check the communication status of the fieldbus. Refer to the chapter Fieldbus Control, or the Fieldbus Adapter manual.

    Check the parameter settings:

    Group 51 COMM Module Data (for fieldbus adapters).

    Group 52 Standard Modbus (for standard Modbus bus links).

    Check the fault function parameters.

    Check the cable connections.

    Check whether the host is able to communicate.

    Ok thanks.

  8. Anonymous users2024-01-29

    ABB ACS800 inverter reported 7510 what is the reason?

    7510 is an alarm for a computer hardware failure**. This fault alarm indicates a hardware fault in the ACS800 drive. The specific cause of the failure could be:

    1. The hardware of the computer is faulty, such as the failure of the controller or peripheral equipment; 2. The system program of the computer has the wrong age or has been damaged; 3. Three-phase AC power supply is short-circuited or the power supply is lost. To find out the cause of this failure, the inverter should be turned off, the power wiring and peripheral equipment should be checked, the problematic parts should be checked and replaced, and the inverter system program should be reloaded; If there is an error in the system program, it should be reported to the manufacturer immediately and the valid program should be replaced.

  9. Anonymous users2024-01-28

    What does ABB ACS580 fault **7122 mean? How to solve it?

    Check whether the power supply of the brake is normal; Check whether the mechanical transmission of the brake is normal; Check for brake coil failure; Check the brake limit and return signal slip finger carefully; Check whether the contactor is normal; The contactor Xinjing main electrical failure, is caused by a contact contact is not good or the contact terminal screw is loose, take repair and replace the new components, the brake damage should be taken from the new line and replaced, pay attention to the original model and parameters when replacing, I hope to help you! If you are satisfied with my service, thank you for giving me a thumbs up with your precious fortune hand.

  10. Anonymous users2024-01-27

    Summary. Hello dear, ABB inverter D107 fault causes and solutions are as follows: inverter failure is divided into two kinds, one is false alarm (inverter can work normally), the other is fault (inverter can not work normally, usually off2 stops) Whether the alarm or fault will appear corresponding failure**, according to the fault ** view the manual, according to the guidance on the manual can basically find the cause of the failure, and deal with it <>

    ABB880 inverter fault**D107

    Hello dear, ABB inverter D107 fault causes and solutions are as follows: inverter failure is divided into two kinds, one is false alarm (inverter can work normally), the other is fault (inverter can not work normally, usually off2 stops) Whether the alarm or fault will appear corresponding failure**, according to the fault ** view the manual, according to the guidance on the manual can basically find the cause of the failure, and deal with it <>

    ABB880 inverter failure**D107 brake failure fault causes: the brake action is insufficient, the stop signal limit does not work, and the brake mechanical failure. Workaround:

    Check whether the power supply of the brake is normal; Check whether the mechanical transmission of the brake is normal; Check the fault of the brake coil, check the limit and return signal of the brake; Check if the contactor is normal The main electrical fault of the contactor is that a certain contact is not in good contact, the screw of the contact terminal is loose, and the new part is repaired for replacement. When the brake is damaged, replace it with a new one off the assembly line and replace it, and pay attention to the original model and parameters when replacing.

  11. Anonymous users2024-01-26

    Summary. Hello, glad to answer for you. Dear, ABB two inverters switch when 7310 overspeed troubleshooting; The load on the motor end exceeds the rated power. Adjust the load to avoid overloading. Or add a braking resistor.

    Hello, glad to answer for you. Dear, ABB two inverters switch when 7310 overspeed troubleshooting; The negative load of the motor side exceeds the rated spine power. Adjust the load to avoid overloading. Or add a braking resistor. World Fight.

    The inverter drag system is unstable. This needs to check the gain parameters and adjust them reasonably. 3.Overspeed detection equipment failure. This is the detection of false positives. If it is a telegram, it will be reported to Kibi, and the argument is like repentance. You can change the detection stove banquet module.

    The problem is that when the two inverters switch with the switch button, they will report 7310, and if they will switch, there will be no alarm.

    The load at the end of the motor exceeds the rated power width. Adjust the load to avoid overloading. Or add a braking resistor.

    The inverter drag system is unstable. This needs to detect the lulu or gain parameters, and the adjustment can be reasonable. 3.

    Overspeed detection equipment failure. This is the detection of false positives. If it's a call, it's basically all.

    You can change the detection module.

Related questions
7 answers2024-02-08

68-71 Borean tundra or howling fjord.

71-74 Dragonbone Wilds. >>>More

8 answers2024-02-08

There are a total of 7 movies for Batman (counting next year's Rise of the Dark Knight). The first 4 parts are one, and the last three parts are one.

8 answers2024-02-08

Castle Ghost Castle Ghost das Spukschlo? im spessart(1960) >>>More

68 answers2024-02-08

I think it's trust, if you're always suspicious with him, there's no need to talk about it, only a breakup, it's not that bad to pull, 2 copies, maybe it's a souvenir for yourself, it's a put, if it's really no way, you can test it, say how good this gift is, ask him ** bought. If you tell the truth, you can ask openly, there are ghosts when you lie, you should pay attention to the point! But don't expose him, if you expose it, there will be no way out, it should be a temptation is not necessarily the truth, there may be errors, haha, the little brother's foolish opinion, I hope it will help my sister!

21 answers2024-02-08

Drink white first, drink beer, if not, then come to red, the effect is good, you can style.