Gree air conditioner display E2 is anti-freezing protection, plate heat exchanger anti-freezing protection, evaporator anti-freezing protection, anti-low temperature, the specific cause of the fault needs professional service personnel to come to the door to detect and troubleshoot, please click on the self-service report or call Gree national unified after-sales service**4008365315 feedback your needs and suggestions.
-
Solution:1Clean the filter before the evaporator.
2.Take off the antifreeze thermometer head of the internal unit and put it in hot water, turn on the machine for trial operation, if E2 is not displayed, then there is a problem with the sensor and needs to be replaced.
3.If all of the above is normal, it means that there is a problem with the circuit board and needs to be replaced.
The meaning of the E2 failure of the Gree air conditioner: anti-freezing protection.
1.Anti-freezing protection means that when the evaporator temperature is too low, the air conditioner enters a protective state in order to protect itself.
2.In the refrigeration and dehumidification mode, the compressor starts for 6min, and when the T steamer<-5 is detected for 3min continuously, the indicator light flashes and shows the fault **E2 and the CPU will issue a command: stop the compressor and external fan, and do not shield the buttons.
3.When T steaming》6 and the compressor has been stopped for 3min, the indicator light is off, the LCD recovery display, and the original state is running.
-
The meaning of the E2 displayed by Gree air conditioner is that the air conditioner has entered the state of anti-freezing protection, which is that the evaporator temperature of the air conditioner is too low, and the cold air dissipation capacity of the air conditioner is insufficient, and the air conditioner filter needs to be cleaned.
A few common causes of anti-freeze protection:
1. The filter screen is dirty and blocked.
2. The surface of the evaporator is dirty and the air volume is small.
3. Lack of fluorine in the system.
4. There is a flattened place in the connecting pipe.
5. The indoor fan does not rotate or the tuyere is blocked.
6. The indoor ambient temperature is lower than 18 degrees.
7. The temperature sensing head of the tube is broken.
8. The plug of the tube temperature sensing head is not plugged in properly.
Fast power mode: each line functionLine 1: Negative control signal of phase w; Line 2: the positive end of the control signal of W;
Line 3: V's negative end control signal; Line 4: V positive end control signal;
Line 5: U's negative end control signal; Line 6: U positive end control signal;
Line 7: ground wire; Line 8; +5V line; Line 9: +12V line;
Line 10: module protection signal line [module protection has: overheating, overcurrent, undervoltage protection, and the module has a microsecond signal output during protection].
-
Answer: The E2 failure of the Gree air conditioner refers to the failure of the anti-freezing protection of the evaporator, the reason for this situation may be caused by the indoor fan not turning or the air outlet is blocked, or it may be caused by the indoor ambient temperature temperature below 18 degrees, or it may be caused by the broken head of the tube temperature sensor, or because the plug of the pipe temperature sensor head is not plugged in properly, and if it is caused by the abnormal control loop, it will also lead to the E2 failure of the Gree air conditioner.
Here's how to fix it:
1. If the indoor fan does not rotate or the tuyere is blocked, it needs to be dredged.
2. If the indoor ambient temperature is lower than 18 degrees, it needs to be adjusted.
3. If the tube temperature sensing head is broken, it needs to be repaired.
4. If the plug of the tube temperature sensor is not plugged in well, it needs to be plugged in.
5. If the control loop is abnormal, you need to contact the professional after-sales service personnel of Gree Air Conditioner for on-site inspection and maintenance.
-
Gree air conditioner display E2 is anti-freezing protection plate heat exchanger anti-freezing protection evaporator anti-freezing protection anti-low temperature, the specific cause of the fault needs to be detected and dealt with by service personnel, please click "Appointment Service" or call the national unified after-sales service ** feedback your suggestions and needs.
-
What is the reason for the appearance of E2 in the air conditioner.
-
After running for a period of time, the compressor and outdoor fan are stopped, and the indoor fan is still running, and the fault is displayed**E2 (no display for light box type):
1) Check whether the evaporator is frosted, if it is frosted, it will show fault **e2. The causes of frosting may be:
1) If the system lacks fluorine, the pressure gauge can be used to measure the system pressure, and the operating current can be measured with a clamp meter.
2) When the temperature is low (below 25), frost may form in the evaporator during refrigeration operation.
3) The surface of the evaporator is dirty and the air volume is small.
2) If the evaporator is not frosted, it may be that the position of the indoor tube temperature head is wrong, resulting in the local temperature being too low, and the tube temperature head can be moved out and tried again.
3) The indoor tube temperature sensor package is broken or broken.
4) It could also be a malfunction of the display itself or a problem with the control board.
5) The filter is too dirty.
6) The system is dirty and blocked.
7) Indoor motor speed is too low.
-
Gree air conditioner display E2 means "internal unit anti-freeze protection". That is, when the evaporator temperature is too low, the air conditioner enters a protective state in order to protect itself. If there is no problem with the temperature sensing head when E2 occurs, it means that the evaporator is dirty or the air speed of the internal unit is too low.
A few common causes of antifreeze protection and solutions:
1. The filter screen is dirty and blocked, and it can be solved by cleaning the filter screen.
2. The surface of the evaporator is dirty and the air volume is small. Clean the evaporator and you'll be fine.
3. System failure. When the evaporator of the internal machine is frosted during normal operation, it means that the system is faulty. Remove the chamber tube thermob from the evaporator. If e2 does not appear after removal, it is also a system failure. Need to find after-sales maintenance.
4. Control system failure. When the internal evaporator does not frost during normal operation, and the pressure (normal) is also normal, it means that there is a problem with the tube temperature sensor in the control system and needs to be repaired after sale.
Workaround for e2 to appear:
1. Check the filter. If it is dirty, it needs to be cleaned, and if it is not, the internal evaporator needs to be cleaned.
2. Analyze whether it is a control failure or a system failure
First look at whether there is frost in the evaporator of the internal machine during normal operation, if it is frosty, it means that the system is faulty. Remove the chamber tube thermob from the evaporator, if E2 does not appear, it means that there is a system problem.
If there is no frost and the pressure (which is normal) is normal, there is a problem with the tube temperature sensor in the control system.
3. Check whether the indoor ambient temperature is too low, whether the speed of the indoor fan is too low, whether the indoor evaporator is too dirty, whether the system is blocked, and whether the inner pipe thermometer is misprotected due to open circuit.
-
Hello, glad to answer for you. The easiest way to deal with Gree air conditioner E2 is 1. If the Gree cabinet machine fails, you can check the fault**, operate according to the manual, and cannot solve it by yourself, it is recommended to contact the after-sales service directly. 2. The Gree cabinet machine cannot be refrigerated, it may be a condenser failure, it is recommended to contact the after-sales maintenance.
3. The filter screen of the Gree cabinet code dust sensitive machine should be cleaned regularly, and the filter screen is damaged and needs to be replaced in time. 4. Do not blow directly on the Gree cabinet machine, which is not conducive to human health, and the cold air needs to blow upwards during daily use. 5. The Gree cabinet machine has different modes, and when used at night, the night mode can be turned on, which is conducive to saving electricity.
6. The Gree cabinet machine should not be started frequently, it will not delay the branch and save electricity, and it will also affect the service life of the compressor.
-
<> Gree air conditioner E2 means that it has entered the state of anti-freezing protection. Solution: Check the filter screen first, if it is dirty, it needs to be cleaned, if Nian Nian Li is not dirty Gao Feng, then clean the evaporator of the internal machine.
Then take a look at whether there is frost in the evaporator of the internal machine during normal operation, if it is frosty, it means that it is a system failure. If there is a problem with the tube temperature sensor, the tube temperature sensor needs to be serviced.
-
The causes and solutions of Gree air conditioner E2 are: cleaning the air conditioner filter, adjusting the temperature of the air conditioner, checking the connection lines of indoor and outdoor units, removing the dust of the outdoor unit of the air conditioner, and checking the leakage of the air conditioner refrigerant.
1. Clean the air conditioner filter.
The air conditioner filter is a very important part of the air conditioner, which filters dust, bacteria and other pollutants in the indoor air and purifies the air. However, because the filter cannot be reused, it is easy to clog, which affects the refrigeration effect. It is recommended that users clean the air conditioner filter once a quarter to ensure the cooling effect of the air conditioner.
2. Adjust the temperature of the air conditioner.
If the temperature of the air conditioner is too low, it will not only waste energy, but also easily lead to the failure of the Gree air conditioner E2. Therefore, users should adjust the temperature of the air conditioner reasonably and adjust the temperature to a comfortable room temperature, not too low a room temperature. Normally, the temperature of the air conditioner should be between 22 -28, so as to effectively ensure the normal operation of the air conditioner.
3. Check the connection lines of indoor and outdoor machines.
The failure of the Gree air conditioner E2 may also be caused by a poor connection line. Users can check whether the connection between the indoor and outdoor units of the air conditioner is firm, loose or damaged, and replace and reconnect immediately if found. In this way, the occurrence of Gree air conditioner E2 failure can also be avoided.
4. Remove the dust from the outdoor unit of the air conditioner.
After the use of the Gree air conditioning room Chitan outdoor unit for a long time, the dust will accumulate more and more, which will affect the refrigeration effect of the air conditioner and easily lead to E2 failure. Therefore, users should clean the surface dust and dirt of the outdoor unit in time, and can use special cleaning equipment or ordinary wiping cloths to ensure the long-term normal operation of the air conditioner.
5. Check the leakage of refrigerant in the air conditioner.
The failure of the Gree air conditioner E2 may also be caused by the leakage of the air conditioner's refrigerant. Users can observe whether there is refrigerant leakage during the use of the air conditioner by listening and smelling and observing, and take timely measures to repair and replace it. Avoiding refrigerant leakage can effectively prevent the occurrence of Gree air conditioner E2 failure.
-
The failure of Gree air conditioner E2 usually refers to the failure of the indoor temperature sensor or the communication failure of the indoor and outdoor temperature sensor. Here's how to deal with it:
1.Check that the room temperature sensor is damaged or loose, and if so, it needs to be replaced or re-fixed.
2.Check whether the communication line of the indoor and outdoor temperature sensor is normal, if the line is damaged or poorly connected, it needs to be repaired or reconnected to hold Xiaoheng.
3.If the above two situations are ruled out, but the E2 fault still exists, you need to contact a professional air conditioner maintenance personnel for maintenance and repair.
The e-share mode of Gree air conditioner automatically sets the temperature between 26-28 degrees, which can avoid setting too low and running all the time. 1.The e-share mode of Gree air conditioner is based on the environmental sensor of the air conditioner, which will automatically change according to the ambient temperature, which can well avoid low temperature settings and keep running, reduce noise and airflow, and make sleep more comfortable. >>>More
For those commonly used modes on the remote control of Gree air conditioner, especially the cooling mode and heating mode, we are no longer familiar with it, using the cooling mode in summer and the heating mode in winter. Everyone is no stranger to snowflakes and the sun, the snowflakes represent the cooling mode, and the sun represents the heating mode. There are also water droplets that represent the dehumidification mode, which needs to be practical in spring and autumn when the indoor humidity is too high. >>>More
Gree air conditioner heating mode is not.
The causes and solutions of heating are as follows: >>>More
Everyone knows that the air conditioner is controlled by the remote control, and if you are not careful, you will press the wrong button, and the air conditioner remote control will generally have a lock button function to prevent accidental contact and change the operating status of the air conditioner. I don't know if you have encountered the phenomenon of air conditioning being locked in the use of air conditioning, if you encounter this phenomenon of air conditioning locking, how should we solve it? The following will introduce to you the method of air conditioner unlocking, and after learning the method of air conditioner unlocking, you can unlock the air conditioner by yourself. >>>More
What does it mean when the air conditioner shows E1.
After about 8 to 10 minutes of cooling of the open machine, E1 is the fault of the air conditioner (compressor current protection, compressor overheating protection, outdoor unit exhaust temperature too high protection, outdoor unit phase sequence current protection circuit board is broken). >>>More