After using it for a few years, the kitchen leakage protector suddenly tripped without load, how to

Updated on society 2024-06-16
7 answers
  1. Anonymous users2024-02-12

    Leakage protector fault check steps.

    1) Press the test button to see if it can be accurate, fast and reliable action, if it can show that the leakage is good, if it can't mean that the leakage is bad, it should be replaced in time.

    2) If there are more circuits connected to the protector, you can only open the circuits that are known to be operating normally, and see if the leakage warranty is working.

    3) If it is not possible to judge accurately, you can use the method of connecting the false load, disconnect all the loads of the leakage protector and connect the false load without fault, if the leakage action can determine that the leakage warranty has been damaged, and the leakage protector should be replaced.

    2.If the defective warranty is still tripped after the replacement of the leakage, the inspection steps are as follows if the fault point cannot be determined quickly.

    1) Check the main line of the circuit first, throw off all the branches, and use a megohmmeter to test the insulation. On the premise that it is confirmed that it is only a leakage fault and is not too serious, direct power transmission will not cause adverse effects.

    2) After confirming that there is no problem with the main circuit, check each branch line, and check the same method as above.

    3) After finding out the faulty branches, the load of the branch line is eliminated one by one.

    4) Finally, find out the fault point, repair the power transmission and test operation.

    Note: In the event of a leakage fault, frequent power transmission is not allowed without confirming the cause of the fault and troubleshooting. Otherwise, unintended and serious consequences may occur.

  2. Anonymous users2024-02-11

    In the case of no load in the circuit, the leakage protector trips frequently, which indicates that the power supply line itself is faulty, the insulation of the line is reduced, and when the voltage is too high, there will be an instantaneous breakdown, which will trip, and can only be carefully checked or detected with the help of an instrument.

  3. Anonymous users2024-02-10

    There is no load, the leakage protector trips, first remove the leakage protection line, if it also trips the problem is in the leakage protection internal circuit, if the line is removed it is normal, the problem is in the power supply line, the line has the phenomenon of leakage grounding.

  4. Anonymous users2024-02-09

    Without load, the reason why the leakage protector trips frequently is that it is broken.

  5. Anonymous users2024-02-08

    This is because there is leakage in the circuit, and the leakage protector will trip frequently.

  6. Anonymous users2024-02-07

    1. The leakage protector trips normally: if the leakage switch with a rated leakage current of 30mA has a leakage current of more than 25mA in the load, the leakage switch will trip. Since it is safe for a current of 25mA to flow through the human body, no electric shock death will occur; In the same way, there will be no danger to the line or electrical equipment, and the operation of the electrical equipment will not produce abnormal phenomena.

    In this case, without analysis, mistakenly think that there is a problem with the quality of the leakage switch, and arbitrarily remove the leakage switch, which is extremely wrong, after removing the leakage switch, see that the electrical equipment is working normally, it is considered that the removal is correct, which is a dangerous practice. 2. Abnormal tripping of leakage protector: It is caused by the unqualified quality of the leakage switch itself, which is divided into two categories: it cannot be closed and sometimes trips for no reason.

    In the case that the leakage switch is connected to the power supply and not connected to the load, if it cannot be closed, it must be the quality problem of the leakage switch, and it must not be repaired by itself, because the technical performance test must be carried out after repair, and it is not safe to use it after testing with test equipment. The second type is occasional tripping, especially in the middle of the night or when no one is at home, which indicates that the anti-interference performance of the leakage switch is poor. The leakage switch with abnormal tripping should be removed and replaced with a good leakage switch.

    3.If the leakage current of normal tripping fluctuates up and down at 25mA, the phenomenon is similar to occasional tripping, and the reason for the tripping of the leakage protector is often caused by the aging of the insulation of the wire, that is, it trips when the environment is wet, and it does not trip when the environment is dry. A reliable way to distinguish between normal and occasional tripping of this type is to measure the insulation resistance of lines and electrical equipment.

    The standard stipulates that the insulation resistance of each wire shall not be lower, and the insulation resistance of electrical equipment shall usually be greater than that. If the total measured insulation resistance of the load connected to the leakage switch is less, then normal tripping will occur.

  7. Anonymous users2024-02-06

    1.The rated action current of the air switch is too large and the maximum allowable current of the line does not match, and the line has not been short-circuited or has not reached the action current value of the air switch when it is overloaded or partially burned for a long time, so it does not operate. 2.

    The air switch does not have a leakage protection function, so if the wire is not burned due to short circuit or overload, the air opening will not be activated in advance (including the combustion process is not short circuited). 3.Air switch quality problems.

Related questions
9 answers2024-06-16

I have encountered this situation you said, the zero line from the transformer to disconnect the leakage protector will not trip (the reason is that the leakage protector itself needs the live wire zero line to work, see the relevant instructions for details), the home may indeed appear 380 voltage, that is because from the transformer is three-phase electricity, divided to different branches, but the total zero line is common once it is disconnected, between the different phase wires and the phase wires can be through the running electrical appliances to form a loop, That is to say, the line voltage of 380V will be divided into two different electrical appliances (at this time, the electrical appliances are equivalent to being connected in series between two phase wires), but the resistance value of each electrical appliance is different, and the voltage shared by each electrical appliance is different, so theoretically speaking, some electrical appliances can still work normally at this time (when the voltage shared by them is close to the normal value). If all the loads coming out of the transformer can be disconnected, the voltage between the live wire and the neutral wire will be 0 (in fact, at this time, the live wire and the neutral wire are connected through the windings of the electrical appliances and other equivalent to a phase wire).

9 answers2024-06-16

Four reasons. 1. Poor installation of leakage protector If the terminal connection of the leakage protector is not firm during installation, the terminal will heat up and oxidize over time, and the wire insulation layer will be burned out, accompanied by the smell of ignition and rubber and plastic burning, which will cause the circuit to undervoltage and trip the leakage protector. Second, there is a problem with the leakage protector itself. >>>More

25 answers2024-06-16

First, the car battery leakage of about 1% per day, if the connection is not removed from the car, the car is used to maintain the minimum current (commonly known as "dormant" current) about 80mA, if there is an anti-theft alarm, it will also consume a certain amount of electric energy, the general battery has about 2 3% of the electricity consumed every day, charged in three situations: >>>More

18 answers2024-06-16

The differences are as follows:

1. Air switch is our usual familiar name, and its correct name is air circuit breaker. The air circuit breaker is generally low-voltage, that is, the rated working voltage is 1kV. An air circuit breaker is a switchgear with a variety of protection functions that can cut off and turn on the circuit at rated voltage and rated operating current. >>>More

18 answers2024-06-16

Since the principle of the leakage protector is that the current flowing into the leakage protector and out of the leakage protector is equal, the leakage protector will work normally, and the current flowing into the leakage protector and out of the leakage protector is not equal, and the leakage protector will be powered off.