How many water separators are used to install floor heating in a house of about 130 square meters? W

Updated on home 2024-07-13
11 answers
  1. Anonymous users2024-02-12

    My square meter house, when the house was delivered, it was a 7-way water divider, and I felt that the effect was not good after three years, and the far end was not hot. I found someone to clean the pipes and replaced a water separator, Weijia brand, copper one, which is much better than before.

  2. Anonymous users2024-02-11

    One circuit per room. The water separator is recommended to use the two-hand wheel to adjust the or intelligent water separator, do not use the ball valve water separator, otherwise it is inconvenient to adjust the hydraulic balance of each circuit, and the floor heating family that often sees some central heating in the future says that some rooms are not warm enough, many of them are caused by the use of the ball valve water separator can not adjust the hydraulic balance of each circuit. It is recommended to use the brass water separator with Henger warm forging, they only have a two-hand wheel adjustable and intelligent temperature control water separator, not a low-end ball valve water separator.

  3. Anonymous users2024-02-10

    One lap per room. It is recommended to replace the ball valve water separator with two-handed rotation or intelligent water separator, otherwise it will be inconvenient to adjust the hydraulic balance of each circuit. Later, some central heating floor heating families often said that the temperature in some rooms was not enough, and many of them were caused by the inability of the ball valve water separator to adjust the hydraulic balance of each circuit.

    It is recommended to use a brass water separator forged by Henger Nuan.

  4. Anonymous users2024-02-09

    8-way usually requires an 8-way water splitter. In a 120-square-meter house, if the whole house is underfloor heating, it is usually necessary to use an 8-way water divider, which can make each room have a good heating effect, and the price of the 8-way water separator is more affordable, which can greatly save costs. When laying floor heating, it is necessary to choose the appropriate number of water separators according to the area of the house, so that the heating effect will be better.

  5. Anonymous users2024-02-08

    Abstract Hello, 140 square rooms, according to the number of rooms in the space division, set up water separators, generally set up about six ways.

    When installing floor heating, we must install a floor heating water divider, because only the floor heating water divider, we can use floor heating normally. We need to pay attention to the installation of floor heating water separators, because the number of floor heating water separators in different areas is different. If your house is about 140 square meters, then you can consider using a 6-way underfloor heating water divider.

    How many water separators do you need for floor heating in a house with a construction area of 140 square meters Hello, I have seen your question and am preparing an answer, please wait.

    Hello, 140 square rooms, according to the number of rooms in the space division, set up water separators, generally set up about six ways. When installing floor heating, we must install a floor heating water divider, because only the floor heating water divider, we can use floor heating normally. We need to pay attention to the installation of floor heating water separators, because the number of floor heating water separators in different areas is different.

    If your house is about 140 square meters, then you can consider using a 6-way underfloor heating water divider.

  6. Anonymous users2024-02-07

    It is calculated according to 90m per road. 5m。On this basis, there can be slight adjustments.

    100/。According to the actual construction guidelines, according to the calculation of 7 or 8, the pipe that needs to be laid per square meter is about 6, which is also the best value of 100 square meters in actual use, that is to say, each pipe can be appropriately shortened or lengthened. So 100 square is about 7 8-way pipes.

    Here are a few equations for you. This is the area of each road; 14 = 7, about 7 8 ways of floor heating pipes, according to 14 to calculate, a pipe covers about 14 square meters. 14. This is the regulation of the industry.

    8。Typically, the length of each underfloor heating pipe is 90m.

    90, you can count it yourself, generally not beyond the range of 80 100. 5=13;6, this is the number of roads.

  7. Anonymous users2024-02-06

    Recommended on 2017-09-09

    100 square meters, about 7 8 ways of underfloor heating pipes.

    Usually, the length of each floor heating pipe is 90m, which is the industry regulation and the best value in actual use. On this basis, it can be slightly adjusted, that is to say, each pipe can be appropriately shortened or lengthened, generally not beyond the range of 80 100. According to the actual construction guidelines, the pipes that need to be laid per square meter are approximate.

    According to the calculation of 90m per road, a pipe covers about 14 square meters. So 100 square is about 7 8-way pipes. Give you a few equations, and you can do the math yourself.

    90 according to 14. This is the area of each road;

    100 14=, this is the number of roads, calculated according to 7 or 8.

    Follow-up question: The number of meters per square meter, and the number of square meters of the pipe, is it a dead number,,, are they counted like this, and the answer is yes. However, this is a theoretical value, and there are errors in actual operation, so the errors can only be minimized.

    20 You may be interested in.

    What brand is good for looking for floor heating water separator? Only.

  8. Anonymous users2024-02-05

    2-way water separator.

    The construction area is 135 square meters, remove some places that do not pave floor heating, such as balconies, under cabinets, under fixed wardrobes, etc., the actual area of floor heating should be about 80 square meters.

    Loop calculation method: the maximum length of a single loop pipe can not exceed 120 meters, generally controlled within 90 meters, the pipe spacing is generally 15-20 cm or about 6 meters per square, and a loop can be laid 15 squares;

    However, the circuit should also be calculated separately according to each heating area, for example, the master bedroom is controlled by a thermostat alone, and the heating area of the master bedroom is 18 square meters, then it should be equipped with 2-way water separators.

  9. Anonymous users2024-02-04

    The construction area is 135 square meters, remove some places that do not pave floor heating such as balconies, cabinets, fixed wardrobes, etc., the actual area of floor heating should be about 80 square meters, loop calculation method: the maximum length of a single loop pipe can not exceed 120 meters, generally controlled within 90 meters, the pipe spacing is generally 15-20 cm is about 6 meters a square, a circuit can be laid 15 squares, but the loop should also be calculated separately according to each heating area, such as the master bedroom is placed separately a thermostat independent control, the heating area of the master bedroom is 18 square meters, then it should be equipped with 2-way water separators.

  10. Anonymous users2024-02-03

    Do the math how much it will cost you to renovate your home

    When many people install floor heating, they don't know how many ways to use the floor heating water divider, so how many ways is 90 square meters of floor heating? What are the precautions for the installation of floor heating water separators?

    1. 90 square meters of floor heating.

    90 square should use 5-way floor heating water separator, because in the case of a construction area of 90 square meters, the indoor heating area is generally 70 square meters, each square should use the length of the pipe between the destruction of the bureau, each branch in 70 to 80m, then the floor heating water separator is at least 4 ways, but in order to achieve a better heating effect, it is recommended to use a 5-way water separator.

    2. Precautions for installation of floor heating water separator.

    1. The installation of the floor heating water separator needs to be installed before the heating pipe is laid, or synchronously with the water meter and valve, and during the installation process, special fixings need to be used and installed on the wall. After installation, it is necessary to check whether it is firmly fixed, so as to avoid the situation that the floor heating water separator falls off when in use.

    2. In the process of installing the floor heating water divider, the level of the water separator should be ensured, and the installation position of the floor heating water separator should be determined in advance. If it is a semi-duplex type, a water separator should be installed at the high place, or a water separator at the high and low places. If it is a duplex structure, it is necessary to install a water separator on the flat pipe corresponding to the upper and lower floors.

    3. When installing the floor heating water distributor, it is necessary to pay special attention to the connection of the water supply pipe, and control the pipe length of each circuit, so that the pipe length of each circuit can be more uniform, and after the installation of the water distribution pipe, the heating position of each circuit should be indicated to facilitate future use and maintenance.

    Summary of the sale: 90 square meters of floor heating a few ways related content is introduced to you here, in order to make the floor heating play a better effect, we must choose the right way to install, it is recommended to ask professionals to install, so that it will be safer to use. If you want to know more about decoration, you can pay attention to the relevant information of Qeeka Home.

    Enter the area and get the decoration for free**].

  11. Anonymous users2024-02-02

    Summary. Hello dear. A 3-circuit separator is sufficient.

    There are nine ways to have the most floor heating water separators, a normal circuit is calculated according to the area of the pipe laying, the floor heating pipe of the road is calculated according to the pipe length of 75 meters, the spacing is 20 cm, a square meter is laid with a pipe of 4,7 meters, you can lay 15 square meters, if the room at home is 100 square meters, then you need to use 6 circuits of the water separator, for some users who need to install radiators in the bathroom, you can add another group of circuits.

    Hello dear. A 3-circuit separator is sufficient. There are nine ways of floor heating water separator, a normal circuit is calculated according to the area of the pipe laying, the floor heating pipe of the road is calculated according to the pipe length of 75 meters, the spacing is 20 cm, and the pipe of 4,7 meters is used to lay a square meter, you can lay 15 square meters, if the room at home is guessed as 100 square meters, then you need to use the sliding pin of the 6 circuits, for some users who need to install radiators in the bathroom, you can add another group of circuits.

    There are too many channels of the floor heating water separator, and it is easy to have a very serious situation, that is, the water flow in each circuit is insufficient. This is also the most important reason why I personally think that the number of underfloor heating water distributors should not be too much. For example, the water separator of floor heating in our home is a six-way one, so under normal circumstances, the six-way circulation is very good.

    But when we were decorating, we changed it to eight roads, or even ten roads, in fact, you can go to see the final effect of Xi Nianji, and you will find that the effect after changing to ten roads is not good. The fundamental reason is that the total water supply flow does not meet the flow rate of the water circulation in each circuit, that is, the total water supply is limited.

Related questions
16 answers2024-07-13

How much does a 130 square meter renovation cost?

Decoration services are divided into three categories: semi-packaged repair, full-package repair and complete decoration, ** is also subject to change, and the owner can calculate the decoration service according to his own tendency. >>>More

16 answers2024-07-13

Where is it used? Floor height? Home installation?

The installation of the holy island fresh air system is simple, does not damage the indoor furnishings and walls, the overall architectural style, the installation technology is also first-class, to ensure that the installation is risk-free, no damage, and the after-sales maintenance attitude is good, professional, for the after-sales service is guaranteed, is a good product worth reassuring. >>>More

20 answers2024-07-13

Houses with relatively high floor heights are more suitable for installing floor heating, and old houses are more suitable for radiators. For northerners, the most important thing when decorating should be heating. Because the north is very cold in winter, if the heating is not in place, there is no way to survive the winter. >>>More

6 answers2024-07-13

Electric underfloor heating is the main way of heating in winter, and this heating method is now commonly used in our lives, but the types of underfloor heating are also different. Electric underfloor heating is one of them, and the effect is particularly significant. So how much is electric underfloor heating**? >>>More

13 answers2024-07-13

Floor heating is an integrated system, including floor heating pipes, floor heating manifolds and thermostats, wall-hung boilers, etc., such as thermostats and wall-hung boilers are selected according to the specific situation of the user, the thermostat is for room temperature control, and the wall-hung boiler is self-heating for floor heating. Seven Star Comfortable Home, the installation company introduces that there are domestic brands and imported brands of pipes, ** about 100-200 yuan square meters, including installation. Design, survey, etc.