For the unidirectional flow clean room, the method of multiplying the average air velocity and cross-sectional area of the chamber section is used to determine the supply air volume. The cross-section perpendicular to the airflow should be used as the sampling test cross-section, the spacing of the measuring points on the cross-section should not be greater than 5, the number of measurement points should not be less than 5, and the arithmetic average of the wind speed readings of all measurement points should be used as the average wind speed.
For non-unidirectional flow clean room, the air supply volume is determined by the tuyere method or the air duct method, and the method is as follows:
1. The tuyere method is to connect the auxiliary air duct at the tuyere installed with a high-efficiency filter for measurement according to the opening of the tuyere. That is, a straight pipe section with galvanized steel plate or other non-dust-producing materials that is the same as the beginning and inner section of the tuyere, and the length is equal to twice the length of the tuyere, and is connected to the outside of the tuyere. On the outlet plane of the auxiliary air duct, the minimum number of measuring points is not less than 6 points evenly arranged, and the wind speed of each measuring point is measured by using a hot bulby anemometer.
Then, the average wind speed of the tuyere cross-section is multiplied by the net cross-sectional area of the tuyere to calculate the measured air volume.
2. When there is a long branch pipe section on the upwind side of the tuyere, and the hole has been or can be drilled, the air volume can be determined by the air duct method. The measuring section should be located at the part that is greater than or equal to 3 times the pipe diameter or long side length before the local resistance part, and 5 pipe diameters or long side length after the local resistance part.
In the case of rectangular ducts, the measured cross-section is divided into several equal small sections. Each small section should be as close to the square as possible, the side length should not be greater than 200mm, and the measurement point should be located in the center of the small section, but the number of measurement points on the whole section should not be less than 3.
For the circular air duct, the cross-section should be divided into several concentric rings with the same area according to the size of the pipe diameter, and each ring should measure 4 points. Determine the number of rings according to the pipe diameter, and should not be less than 3.
Air volume detection hole, also known as air detection hole, is commonly known as air volume test hole.
The so-called air volume measurement hole refers to a special device for measuring the air volume in the ventilation, dust removal, exhaust pipe or branch pipe, which belongs to the differential pressure measuring instrument for the air volume in the pipeline.
Shanghai Beizhan manufacturing - the measuring port is composed of aluminum alloy or stainless steel KF25 short tube, pagoda joint, fluorine rubber gasket, throttling element, pressure tube and differential pressure gauge, and the throttling element is composed of an air flow inlet plug section, 2 static pressure holes, 1 gradual expansion section and an air flow outlet plug section, and the parts are welded and connected. There is a pressure hole on the hydrostatic ring. The measurement error of air volume in the pipeline is less than 2%.
Air volume measurement device in the branch pipe of the piping system. Generally, these necessary parts and components should be set up in the pipeline to meet the requirements of system technical performance detection, adjustment of relevant parameters and safe operation.
-
Stainless steel pipe Cut off a section and add a plug at one end The air welding spray hole on the air duct can be welded to the air duct.
-
Technical Parameters Material: Zinc Alloy Specification: 60 (length) * 25mm (inner diameter) Metal air volume measurement hole (one-time molding) Suitable for thermal insulation and non-thermal insulation metal air ducts, glass fiber composite air ducts, convenient for air volume and pressure testing.
The code requires that Article 5, 6, 4 of the Code for the Design of Clean Workshops should be provided with pressure measuring holes before and after the medium and high efficiency air filters. On the new air duct and return air main pipe and the branch pipe that needs to adjust the air volume, the air volume measurement hole should be arranged. Recommendations for the installation location of the assay holes:
All air conditioning air supply systems and exhaust systems should be equipped with measuring holes on the main air supply and exhaust pipes, and the measuring holes should be installed about one-third downstream of the airflow direction of the straight pipe section. For the air conditioning air supply system with return air, a measuring hole should be installed on the return air duct and the fresh air duct, and the straight pipe section is selected to determine the stability and uniformity of the cross-section airflow, and the principle of the selected straight pipe is that there are no local resistance parts (elbows, tees, reducers, etc.) in the section, so as to ensure the stability and uniformity of the flow field in the pipe. For rectangular pipes, the pipe section is divided into a number of small rectangles of equal area, and the measuring points are arranged in the center of each small rectangle, and the length of each side of the small rectangle is about 200mm.
A measuring hole is installed in the center of each rectangle. For circular pipes, two measuring holes perpendicular to each other are arranged in the same section.
id=740
Mugwort. It's just not a score.
-
Air volume detection hole, also known as air detection hole, is commonly known as air volume test hole.
The use and precautions of polarimeter:
A before the determination of the instrument and the sample should be placed in a constant temperature chamber of 20 or a constant temperature chamber at a specified temperature, and a constant temperature water bath can also be used to keep the sample chamber or sample test tube above the constant temperature lh, especially some optical rotation substances that have a great impact on the temperature, which is particularly important. >>>More
Loss: Cooking raw and cooked is not appropriate, and not eating is not eating.
Cook the rice below, steam the rice on the top, and cook the rice at the same time!
Hello 1 7 step by step reading.
Prepare the old lotus root, minced pork, salt, cornstarch, and soy sauce. >>>More
In everyday life, there are very many types and brands of shoes, among which there are so many brandsMartin bootsIt's hot, but there are many types and colors of Martin boots, and boys have no requirements for the pants that Martin boots match, but I personally suggest that Martin boots should be matched with some suitable clothes, let's talk about it hereBlack eight-hole martin bootsHow to match pants, it will look betterFunky >>>More