Focus on checking the escape route, the connection of each system equipment and the single use function. The fire hydrant was test-fired and the water pump adapter was filled. Whether the report is normal at the scene.
It is to press the hand report to see if the linkage of each system is normal. Spot check the air pressure and air volume of positive pressure air supply and smoke exhaust. The function of the pump room and the fire control center.
It is also necessary to test the quality and identification of fire protection product materials on the spot according to the reported product information. For the problems on the fire inspection report, focus on inspection.
Extended information: fire acceptance refers to the fire department of enterprises and institutions when the completion of the fire inspection of the qualified investigation, the construction unit to carry out fire protection acceptance needs the fire bureau to carry out safety inspection, at the same time need to issue electrical fire inspection certificate, electrical fire inspection has been included in the Ministry of Public Security fire acceptance compulsory inspection items.
The fire department of the public security organ shall organize the fire protection acceptance of the construction project in accordance with the fire protection acceptance assessment standards for the construction project that has passed the fire protection design review. For construction projects that are qualified in the comprehensive assessment, the fire department of the public security organ shall issue a qualified opinion on fire protection acceptance; If the comprehensive assessment conclusion is unqualified, an unqualified opinion on fire protection acceptance shall be issued and the reasons shall be explained.
-
Fire Acceptance Procedures for Construction Projects:
1. After the completion of the construction project, the construction unit shall submit an application for fire protection acceptance of the completion of the project to the public security and fire protection agency, and it can only be put into use after the experience is qualified.
2. After the public security and fire protection agency accepts the case, the specific person in charge of the acceptance shall check whether the information meets the requirements, and if it does not meet the requirements, it shall promptly inform the applicant to make up for it, and notify the construction unit to make relevant preparations before acceptance 1-2 days before acceptance.
3. According to the provisions of the fire engineering acceptance procedures, the fire supervisors of not less than two people shall go to the scene for acceptance, and the fire supervisors participating in the acceptance shall wear standard police uniforms and wear the "Public Security Fire Supervision and Inspection Certificate", and the specific acceptance procedures are as follows:
1) The introduction of each unit participating in the acceptance. The construction unit introduces the general situation and self-inspection of the project, the design unit introduces the design of the fire protection project, the construction unit introduces the construction and commissioning of the project, the supervision unit introduces the project supervision, and the testing unit introduces the testing situation. Click here for free ** construction technical information.
2) Group on-site inspection and acceptance. The acceptance personnel should inspect and test at the same time, and truthfully fill in the fire acceptance record form.
3) Summarize the acceptance situation. Each team reported on the acceptance situation, according to the "Guangdong Province Construction Engineering Fire Protection Acceptance Assessment Rules (Trial)" formulated by the corps, according to the sub-item, single, comprehensive procedures for assessment, the evaluation conclusion is truthfully recorded in the acceptance record form, and the preliminary opinions to the construction, construction, design and other participating acceptance units are proposed, and the rectification opinions that do not meet the requirements of the specifications should be submitted to the construction unit in a timely manner.
4. When the construction, construction and design units participating in the acceptance express their opinions or raise questions, the acceptance participants of the fire protection agency shall give a reply, and if they cannot reply on the spot, they shall give an explanation.
5. After the acceptance or re-inspection of the fire protection project, the acceptance personnel of each unit and the personnel participating in the acceptance of the fire protection agency shall sign the acceptance declaration form.
6. The project acceptance undertaker shall fill in the acceptance opinion in a timely manner, submit the approval form, and sort out the acceptance file and send it to the leader for approval.
7. The construction unit goes to the window and issues a receipt to retrieve the acceptance opinion;
8. When the acceptance and review are unqualified, the construction unit shall organize all relevant units to rectify the problems raised in the "Construction Engineering Fire Protection Acceptance Opinion", and apply for re-inspection to the public fire protection agency after the rectification is completed, and the re-inspection procedure is the same as the application acceptance procedure.
-
2022 New Code for Fire Acceptance:
1. The competent department of housing and urban-rural development is responsible for guiding and supervising the review and acceptance of fire protection design of national construction projects.
2. The competent department of housing and urban-rural construction of local people at or above the county level (hereinafter referred to as the competent department for fire protection design review and acceptance) shall undertake the fire protection design review, fire protection acceptance, filing and random inspection of construction projects within their respective administrative areas in accordance with their duties.
3. The fire protection design review, fire protection acceptance, filing and random inspection of the cross-administrative regional construction project shall be designated by the competent department at the next higher level in charge of the fire protection design review and acceptance department of the administrative region where the construction project is located.
4. The competent department for fire protection design review and acceptance shall use Internet technology and other information means to carry out fire protection design review, fire protection acceptance, filing and spot checks, establish and improve the credit management system of relevant units and practitioners, and continuously improve the level of government services.
5. The funds required by the competent department for fire protection design review and acceptance to implement fire protection design review, fire protection acceptance, filing and random inspection shall be implemented in accordance with the provisions of the Administrative Licensing Law of the People's Republic of China and other relevant laws and regulations.
6. The competent department for fire protection design review and acceptance shall promptly inform the fire rescue agency of the fire protection acceptance, filing and spot check, and share the building plan, fire protection facility layout plan, fire protection facility system diagram and other information with the fire rescue agency.
7. The staff engaged in the review and acceptance of fire protection design of construction projects, as well as the employees of construction, design, construction, engineering supervision, technical services and other units, shall have the corresponding professional and technical ability and regularly participate in vocational training.
8. The technical service institutions that provide services such as technical review of fire protection design drawings of construction projects, testing of fire protection facilities or on-site assessment of fire protection acceptance of construction projects shall provide services in accordance with the laws and regulations of construction projects, national fire protection technical standards for engineering construction and relevant national regulations, and shall be responsible for the opinions or reports issued.
-
Acceptance basis. Fire Protection Law of the People's Republic of China;
Fire protection acceptance evaluation standards for construction projects》 ;
Regulations on the Supervision and Administration of Fire Protection of Construction Projects" and other fire regulations.
2- Fire protection design of various mechanical and electrical specialties.
1. For each fireproof partition of each floor of a multi-storey building and a high-rise industrial building, when its ventilation and air conditioning systems are set independently, there is no fire damper at the junction of the horizontal air supply and return air duct and the main pipe in the protected fireproof partition;
2. The battery can be used as the backup power supply for the fire accident lighting and evacuation indication signs, but the continuous power supply time should not be less than 20min;
3. Fire lighting should be set up in the following closed stairwells, smoke-proof stairwells and their front rooms, and fire elevator front rooms;
4. Evacuation walkways for closed stairwells or smoke-proof stairwells should be set up according to regulations;
5. The minimum illumination of accident lighting for evacuation should not be lower. The lighting branch line of the fire control room, the fire pump room and the self-provided generator room should be connected to the fire distribution line;
6. Scattered signs should be placed on the top of the Taiping Gate or on the wall below the height of 1m from the ground at the corner of the evacuation walkway, and the spacing of the indication signs on the walkway should not be greater than 20m.
3- Automatic fire alarm and elimination control room.
1. The alarm area is divided according to the fire prevention area, and an alarm area can be composed of several fire prevention zones;
2. The forms of automatic fire alarm system are: centralized alarm system: regional alarm system; Control alarm system (elimination control center), a regional alarm controller can alert multiple floors (see the function of the product) The installation position is meters from the ground, and the installation position of the alarm is meters;
3. Underground shops with a construction area of more than 500m should be equipped with automatic fire alarm devices;
4. The fire resistance level of the independently set fire control room shall not be lower than the second level. Adopt partition walls with fire resistance limits of not less than 3h and floor slabs of 2h respectively, and separate them from other parts and set up safety exits directly to the outside;
5. The fire control room should be equipped with the following functions: receiving fire alarms, sending out fire sound and light signals, accident broadcasting and safety evacuation instructions, etc.: controlling fire pumps, fixed fire extinguishing devices, ventilation and air conditioning systems, electric fire doors, valves, fire shutters, smoke prevention and exhaust facilities.
Display power supply, fire elevator operation, etc.;
-
Summary. Hello dear, I'm glad I answered this question for you. Legal Analysis:
1. The construction area of more than 10,000 square meters must be reviewed and accepted; 2. Less than 10,000 square meters of record spot checks, there are also seventy or eighty percent of the possibility, in short, the possibility is very high, as long as it is a hotel, it will almost have to be accepted; 3. After that, it is necessary to carry out a pre-opening inspection of fire protection. The new regulations in 2022 require the legal basis for secondary fire protection acceptance: Article 12 of the Fire Protection Law of the People's Republic of China If a special construction project has not been reviewed for fire protection design or fails to pass the review, the construction unit and the construction unit shall not carry out construction; For other construction projects, if the construction unit fails to provide fire protection design drawings and technical data to meet the construction needs, the relevant departments shall not issue a construction permit or approve the commencement report.
Article 14 The specific measures for fire protection design review, fire protection acceptance, filing and random inspection of construction projects shall be prescribed by the competent departments of housing and urban-rural construction.
Hello dear, I'm glad I answered this question for you. Legal analysis: 1. The construction area of more than 10,000 square meters must be reviewed and accepted; 2. Less than 10,000 square meters of record spot checks, there are also seventy or eighty percent of the possibility, in short, the possibility of the beginning of the manuscript is very important, as long as it is a hotel, it is almost to be accepted; 3. After that, it is necessary to carry out a pre-opening inspection of fire protection.
The new regulations in 2022 require a legal basis for secondary fire protection acceptance: Article 12 of the draft of the Fire Protection Law of the People's Republic of China If a special construction project has not been reviewed for fire protection design or is unqualified, the construction unit and the construction unit shall not carry out construction; For other construction projects, if the construction unit fails to provide fire protection design drawings and technical data to meet the construction needs, the relevant departments shall not issue a construction permit or approve the commencement report. Article 14 The specific measures for fire protection design review, fire protection acceptance, filing and random inspection of construction projects shall be prescribed by the competent departments of housing and urban-rural construction.
If my answer was helpful, please give <> like
Big Red Clan] <>
Comment in the lower left corner), look forward to your praise, your efforts are very important to me, and your support hall is also the driving force for my progress. If you feel that my answer is still satisfactory, you can click on my avatar for one-on-one consultation. Finally, I wish you good health and a happy mood!
Only candidates who have participated in the national unified examination and have the score line of the re-examination of the enrollment unit can have the opportunity to adjust; Candidates can go to the graduate schools of various colleges and universities ** Adjustment application formCandidates can pay attention to the western colleges and universities or colleges and universities with more adjustment places in previous years. Because there are many good schools in the west, due to the small number of applicants, the hope of being adjusted is relatively large, and you should pay attention to being concise and clear when writing an application for adjustment, and you can introduce your professional background or academic achievements with it. The content of some candidates' adjustment applications is too complicated, and they even write down the words that they regret that they are not in a good state when they are in graduate school. >>>More
Now that fire and rescue is under local management, you may be asking about the time when the conscripts will be discharged. >>>More
The order is different in different areas, generally reversing into the garage, side parking, half-slope, right-angle turning, and curve driving. >>>More
No one.
Checking the announcement published on the official website of China's Internet Police Administration, it can be learned that starting in 2022, the state will implement a zero-tolerance policy on online gambling. >>>More
Licensed Pharmacist Registration Process:
1.After the academic qualification verification is successful, select the qualification exam you need to apply for, enter the page and select the province where you are located, and click Next to enter. >>>More